![ABB DCS800 Скачать руководство пользователя страница 42](http://html.mh-extra.com/html/abb/dcs800/dcs800_installation-manual_3333042.webp)
42
Electrical Installation
WARNING!
The electrical installation described in this chapter should only be carried out by a
qualified electrician. The
at the beginning of this manual must be
followed.
Negligence of these instructions can cause injury or death.
Attention:
Additional information about this chapter especially regarding EMC can be found in
the manual
Technical Guide
(3ADW000163).
Insulation Checks
Every DCS800-A Enclosed Converter has been tested for insulation between main
armature circuit and cabinet at the factory. Therefore there is no need to check the
insulation of the unit again. When checking the insulation of the whole installation,
proceed in the following manner:
WARNING!
Insulation checks must be performed before connecting the DCS800-A to the
mains. Before proceeding with the insulation resistance measurements make sure
that the DCS800-A is disconnected from the mains.
1.)
Check that the motor cable is disconnected from the DCS800-A
output terminals C1 and D1.
2.)
Measure the insulation resistances of motor cable and the motor
between each phase and Protective Earth (PE), using a measuring
voltage at least equal to the mains voltage, but not higher than 500
VDC. The insulation resistance must be higher than 1 M
Ω
.
Mains Fuses
Fuses are needed to protect the DC converter in case of an internal short circuit.
The DCS800-A Enclosed Converter is equipped with internal input fuses. For more
information see manuals
DCS800 Technical Catalogue
(3ADW000192) and
DCS800 Hardware Manual
(3ADW000194). If a fuse is blown, it must be replaced
with the proper ultra rapid fuse.
Electrical Installation
3ADW000352R0101 DCS800-A Installation Manual e a
Содержание DCS800
Страница 1: ...DCS800 Installation Manual DCS800 A Enclosed Converters 18 to 9800 A 19600 A ...
Страница 26: ...26 Cabinet 400 mm width 600 mm depth Mechanical Installation 3ADW000352R0101 DCS800 A Installation Manual e a ...
Страница 69: ...69 Preventive Maintenance 3ADW000352R0101 DCS800 A Installation Manual e a ...