Air Duct Outlet for Enclosed Converters with D6 / D7 Modules
Converter modules size D6 / D7 installed in
cabinets DCS800-A produce a considerable
amount of power loss to be removed by air
cooling. In most cases the switch room is not
capable to absorb the heated air. That is why
cabinets with converter modules sizes D6 / D7
are provided with an adapter for connection to an
air duct (air duct to be supplied for by customer).
Air duct outlet
Air duct
Air
ventilation
hood
Air duct for D6 / D7 module
In case there is no air duct, the option Air
Ventilation Hood is required to meet protection
class IP 21.
Air
(option)
Cabinet
with
D6/D7
module
This option can also be used for connection to an
existing air duct outlet (solution indicated by
dashed lines).
Wall
Air baffle plates
To keep the converter module as cool as possible cooling air re-circulation outside
and inside the cabinet has to be prevented.
To prevent outside cooling air re-circulation external measures have to made.
To prevent inside cooling air re-circulation air baffle plates are used:
COOL AREA
Main air flow in
Main air flow out
Hot
Air baffle plates
prev recirc.dsf
Air baffle plates
Mechanical Installation
3ADW000352R0101 DCS800-A Installation Manual e a