80
Exchange of SDCS-CON-4
3ADW000195R0501 DCS800 Service Manual e e
Install the
new SDCS-
CON-4
1.
Reconnect the flat cables at the SDCS-CON-4 (X12, X13, X37),
2.
Reconnect all I/O plugs at the SDCS-CON-4 (X3 to X7) and the plugs at the
SDCS-DSL-4 (X51 to X54) and
3.
Reinstall the intermediate cover, all plug in options and the design cover.
5.
Set type code of the drive
Follow the instructions in chapter
Set type code
.
6.
Enable application program
If a SDCS-MEM-8 (Memory Card) is used the application program must be
enabled before the parameters are downloaded. Set:
ParApplSave (16.06) = EnableAppl
7.
Download and compare parameters
Parameters can be downloaded and compared by various means:
DCS Control
Panel
Press Soft key 1 until the main menu is shown,
Press LOC/REM button, display will show LOC on the upper left side,
Press Soft key 2 (MENU),
Scroll with UP / DOWN buttons to menu item PAR BACKUP,
Confirm with Soft key 2 (ENTER),
Select DOWNLOAD FULL SET and confirm with Soft key 2 (SEL), the
download progress bar will be shown on the display,
Successful download will be shown by message,
Confirm with Soft key 1 (OK),
Press LOC/REM button, display will show REM on the upper left side,
Press Soft key 1 until back to the main menu and
The actual parameter set is now downloaded into the new SDCS-CON-4.
DriveWindow
Light
Click File then Open…
Choose correct parameter file and click Open:
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]