132
Service
3ADW000195R0501 DCS800 Service Manual e e
To change the type code individually follow the instructions below:
un-protect the type code by means of ServiceMode (99.06) = SetTypeCode
set the type code individually by means of
S ConvScaleCur (97.02),
S ConvScaleVolt (97.03),
S MaxBrdgTemp (97.04) and
S BlockBridge2 (97.07)
the change of the type code is immediately taken over and ServiceMode
(99.06) has to be set back to NormalMode by the user
the new values can be seen in group 4
ConvNomCur (4.05),
ConvNomVolt (4.04),
MaxBridgeTemp (4.17) and
QuadrantType (4.15)