28
30
33
29
31
32
34
D I S TR I B UTI O N SO LUTI O N S
23
9.4.3. Main circuit connection
First route all the cables through the cable gland
(28) before connecting the high voltage cables to
the circuit breaker. After this, crimp the terminals
(29) over each cable (30) according to the
specifications (depending on the cable diameter
and current). Before crimping, make sure that the
9.4.4. Auxiliary circuit connection
Each enclosure is equipped with a Harting-type
connector (standard version). The enclosure can be
equipped with circular-shaped connectors on
request.
size of the chosen terminals allows these latter to
pass through the holes in the enclosure.
First connect the lower cables to the busbar (31) and
tighten them with M12 screws (32) and 84 Nm
tightening torque. Now connect the upper cables to
the busbar (33) and tighten them with M12 screws
(34) and 84 Nm tightening torque. Lastly,
Содержание DCBreak 1815