D I S TR I B UTI O N SO LUTI O N S
9
Actuator characteristics
Closing
Holding
Unom
Umin
Umax
Rnom
Inom
(1)
Imin
(2)
Imax
(3)
R1
Inom
Imin
Imax
Pmax
R1
(4)
Microswitch to protect closing/
opening control system of DCBreak
circuit breaker (recommended)
[V]
[V]
[V]
[Ω]
[A]
[A]
[A]
[Ω]
[A]
[A]
[A]
[W]
ABB N°
24
16.8
30
0.55
43.6
25.1
71.3
7.5
3.0
2.1
3.8
107
S201-K10
36
25.2
45
1.39
25.9
14.9
42.3
18
1.9
1.3
2.37
98
S201-K6
48
33.6
60
1.8
26.7
15.4
43.6
28
1.6
1.1
2.1
118
S201-K6
72
50.4
90
4.9
14.7
8.5
24
68
1.0
0.7
1.25
107
S202-K4
110
77
137.5
12.25
9.0
5.2
12.8
160
0.6
0.4
0.8
105
S202-K2
Power consumption (W)
1060
430
2170
4.92
2.8
9.37
(1) Coil temperature 20 °C
(2) Coil temperature 70 °C and Umin
(3) Coil temperature -25 °C and Umax
(4) R1 = holding resistor (should be 200 W)
6.5. Auxiliary contacts
Designation
Name
Unit
Value
Remarks / conditions
Terminals
Screw with spring washer
Rated insulation voltage
Ui
V
400
Rated impulse withstand voltage
Uimp
kV
4
Thermal current
Ith
A
10
Minimum current
Imin
mA
5
If < 5 mA, gold alloy (on request)
Contact material
Hard silver
(AgCu3)
gold alloy (AuAg26Ni3)
Contact resistance
mΩ
10
Normal
Mechanical life
10 x 106
Max. breaking capacity
Direct current electric power
24 V DC
no
yes
>16 A
>16 A
>16 A
>16 A
15 A
>16 A
12 A
>16 A
10 A
>16 A
8 A
>16 A
110 V DC
no yes
4 A
7 A
3 A 5.5 A
1.7 A
4 A
1 A
3 A
0.6 A
2 A
0.4 A 1.5 A
T
im
e c
o
ns
ta
nt U
R
Switching
voltage (U)
Blowout
5 ms
10 ms
20 ms
30 ms
40 ms
50 ms
Содержание DCBreak 1815
Страница 31: ...DISTRIBUTION SOLUTIONS 31 Notes ...