Ch a p tER 5
Configuring the sensor head
You can configure the sensor head once it has been properly installed in the transformer. The following
pages explain the proper method to do so.
Connecting a laptop for the first time
The first time you connect a laptop to your system:
1
Power up your laptop.
2
Connect the laptop to the
service
Ethernet port using a straight Ethernet cable. For the location of
the Ethernet port, see Figure 3 “CoreSense port and relay connections” on page 21.
The sensor service Ethernet port is configured as a DHCP server and will assign a valid IP address
automatically to your laptop.
NOTICE
Do not
connect your internal network to the SERVICE port.
3
Start up your web browser (recommended: Internet Explorer 9 or above).
4
Direct your web browser to
http://172.16.100.1
to connect to the web interface.
Содержание CoreSense
Страница 1: ... USER GUIDE CoreSense Hydrogen and Moisture Sensor ...
Страница 10: ...Page intentionally left blank ...
Страница 32: ...Page intentionally left blank ...
Страница 37: ... Configuring the sensor head 33 Figure 17 Settings tab Help Provides access to system information ...
Страница 43: ... Configuring the sensor head 39 About dialog box Figure 23 About dialog box ...
Страница 48: ...Page intentionally left blank ...
Страница 58: ...Page intentionally left blank ...
Страница 80: ...Page intentionally left blank ...
Страница 84: ...Page intentionally left blank ...
Страница 106: ...Page intentionally left blank ...
Страница 108: ...Page intentionally left blank ...
Страница 110: ...Page intentionally left blank ...
Страница 114: ...Page intentionally left blank ...
Страница 120: ...Page intentionally left blank ...
Страница 121: ......