ControlMaster CM30, CM50 and CMF310
Universal process controllers,
1
/
4
,
1
/
2
DIN and fieldmount
8 Templates and Functionality
88
IM/CM/ED–EN Rev. X
8 Templates and Functionality
8.1 Basic Templates
8.1.1 Single Loop / Single Loop with Remote Setpoint
This template provides basic feedback control using three-term PID or On/Off control. The controller output
is calculated from the difference between the process variable and the control setpoint. The control setpoint
can be a fixed value entered by the user (Local setpoint) or an input from a remote source (remote setpoint).
Notes.
Input assignments can be changed in
Device Setup
/
Custom Config
– see page 36.
Output assignments can be changed in
Input / Output
configuration – see page 42.
A/M
PV
L/R
SP
AIN 1
AIN 2
x Ratio
+ Bias
LSPT1
LSPT2
LSPT3
LSPT4
Local
Set Point
Manual
Output
Loop 1
PID Control
PID
O/P
OP
Time Prop
Output
Motorized
Valve
Split
Output
AO1
RLY1
RLY2
RLY1
OP2
OP1
Output Type
Analog
Output
1
1
Single Loop + Remote Setpoint only
AIN 3
RSP
FB