![ABB ControlMaster CM30 Скачать руководство пользователя страница 104](http://html.mh-extra.com/html/abb/controlmaster-cm30/controlmaster-cm30_user-manual_2344104.webp)
ControlMaster CM30, CM50 and CMF310
Universal process controllers,
1
/
4
,
1
/
2
DIN and fieldmount
10 Specification
102
IM/CM/ED–EN Rev. X
Outputs
Controls / retransmission outputs
Relays
Digital input / output
2-Wire transmitter power supply
Communications
For MODBUS and Ethernet communications – see
separate User Guide (
).
Infrared port
EMC
Emissions & immunity
Meets requirements of IEC61326 for an
Industrial Environment
Environmental
Operating temperature range
–0 to 55 °C (32 to 131 °F)
Operating humidity range
5 to 95 %RH (non-condensing)
Storage temperature range
–20 to 70 °C (–4 to 158 °F)
Enclosure sealing
CM30 / CM50
CMF310
Vibration (CM30, CM50)
Conforms to EN60068-2-6
Number
CM30 / CM50: 2 (1 standard, 1 optional)
CMF310: 4 (2 standard, 2 optional)
Type
Configurable as analog or digital pulse
Isolation
Galvanically isolated from the rest of the
circuitry, 500 V for 1 minute
Analog
range
0 to 20 mA Programmable
Load 750
Max.
Accuracy
0.25 % of output or
+
/
–
10 µA
Number
CM30: 4 (1 standard, 3 optional)
CM50: 4 (2 standard, 2 optional)
CMF310: 6 (4 standard, 2 optional)
Type
CM30: Standard with changeover
contacts. Optional contacts selectable
as N/O or N/C (by jumper)
CM50: Selectable as N/O or N/C
(by jumper)
Contact
ratings
CM30 / CM50: 5 A, 240 V
CMF310: 2 A 240 V
Update
rate
125 ms
Number
CM30 / 50 / CMF310:
6 (2 standard, 4 optional)
Type
User-programmable as input or output
Minimum input pulse duration – 125 ms
Input
– volt-free
( contact open > 10 M
/
contact closed < 100 k
)
– 24 V DC
(1-signal 15 to 30 V /
0-signal –3 to 5 V)
– TTL
(low: 0 to 0.8 V /
high: 2 to 5 V)
– Conforms to IEC 61131-2
Output
– Open collector output
– 30 V, 100 mA max.
– Conforms to IEC 61131-2
Update
rate
125 ms
Voltage
24 V DC (CM30/50 only)
Number
CM30 / CM50: 2
(1 standard, 1 optional)
CMF310: 1 (optional)
Drive
2 Loops for each transmitter
PSU, 45 mA max.
Baud rate
up to 115 kBaud
Distance
up to 1 m
Functions firmware
upgrade,
configuration
upload / download
Front face
IP66 / NEMA 4X
Rest of enclosure IP20
Front face and
rest of enclosure
IP66 / NEMA 4X