Loop 1 (2) Time Prop
The active time of the output pulse is proportional to the value of the control output. With
100 % output the pulse is active for the complete cycle time, for example:
Note
. Applicable only if
Output Type
is
Time Prop
or
Split Output
(and one output is a relay
or a digital output) – see page 34.
Cycle Time 1
The cycle time to be used with time proportioning outputs.
For
split outputs
this setting applies to
Output 1
– see page
Cycle Time 2
The cycle time to be used with time proportioning outputs.
For split outputs this setting applies to
Output 2
Note
. Applicable only if
Output Type
is
Split Output
.
Alarm 1 (8)
Trip
The alarm trip level in engineering units. See
Process Alarm
(page 58) for parameter details.
Cycle Time
= 10 s
Cycle Time
= 10 s
Cycle Time
= 10 s
50 % Output
10 % Output
90 % Output
5 s
5 s
1 s
1 s
9 s
9 s