![ABB ControlMaster CM30 Скачать руководство пользователя страница 87](http://html.mh-extra.com/html/abb/controlmaster-cm30/controlmaster-cm30_user-manual_2344087.webp)
ControlMaster CM30, CM50 and CMF310
Universal process controllers,
1
/
4
,
1
/
2
DIN and fieldmount
7 Advanced Level
IM/CM/ED–EN Rev. X
85
212.018
NV Error Opt Bd 1
Failure of non-volatile memory on option board
1 or permanent corruption of its data.
CM50 only
Check calibration of AO2, AIN 3 and AIN4.
CMF310
Check calibration of AIN1 and AIN2.
CM50 and CMF310
Recalibrate If necessary. Acknowledge error.
If problem persists contact local service
organization.
210.019
NV Error Opt Bd 2
Failure of non-volatile memory on option board
2 or permanent corruption of its data.
CM30 and CM50
Check calibration of AO2, AIN 3 and AIN4.
CMF310
Check calibration of AIN3 and AIN4.
CM30 / CM50 / CMF310
Recalibrate If necessary. Acknowledge error.
If problem persists contact local service
organization.
208.020
NV Error
Comm Bd
Failure of non-volatile memory on
communications board or permanent
corruption of its data.
Acknowledge error. Check communications
board is correctly identified by device.
If problem persists contact local service
organization.
206.021
NV Error
SW Key 1
Failure of non-volatile memory on Software key
1 or permanent corruption of its data.
Acknowledge error. Check software key
functionality is enabled.
If problem persists contact local service
organization.
204.022
NV Error
SW Key 2
Failure of non-volatile memory on Software key
2 or permanent corruption of its data.
Acknowledge error. Check software key
functionality is enabled.
If problem persists contact local service
organization.
202.023
NV Error
SW Key 3
Failure of non-volatile memory on Software key
3 or permanent corruption of its data.
Acknowledge error. Check software key
functionality is enabled.
If problem persists contact local service
organization.
Config Error
The configuration contains a source that is no
longer present or valid.
Check invalid sources in diagnostics menu –
see Section 7.10, page 83.
Check configuration, check I/O required for
configuration is present and correct any
illegal use of the invalid signal by changing
configuration or fitting additional option
cards.
054.044
(052.045)
Tune Lp1 (2) Fail
Autotune has failed to complete its sequence
or has calculated values outside of its
permitted range.
Check process response. Consider if
Autotune dynamic setting should be
changed. Ensure process is stable and
repeat autotune.
If problem persists tune the loop manually.
062.042
(058.043)
Tune Lp1 (2) Noise
Autotune has failed due to excessive process
or measurement noise.
Check input wiring. Ensure process is stable
and repeat Autotune.
If problem persists, tune the loop manually.
Icon
Number /
Message
Possible Cause
Suggested Action
Table 7.1 Diagnostic Messages (Continued)