![ABB COM600 series Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/abb/com600-series/com600-series_user-configuration-manual_3390418039.webp)
Direction
Data Variable of a Sequence Object
Breaker Data Attributes
->
**.SwitchArray[Index].SwSelectedStatus[1]
*CSWI*/Pos/stSeld
<-
**.SwitchArray[Index].SwSelOn[1]
*CSWI*/Pos/ctlSelOn
<-
**.SwitchArray[Index].SwOperOn[1]
*CSWI*/Pos/ctlOperOn
<-
**.SwitchArray[Index].SwSelOff[1]
*CSWI*/Pos/ctlSelOff
<-
**.SwitchArray[Index].SwOperOff[1]
*CSWI*/Pos/ctlOperOff
->
**.SwitchArray[Index].SwitchMod[1]
*CSWI*/Mod/stVal
->
**.SwitchArray[Index].SwitchHealth[1]
*CSWI*/Health/stVal
Assigning item paths to data objects
4.12.
To assign item paths to data objects:
1.
Select Logic Processor_IED > Sequence logical device > SEQGGIO1 > Str data
object and assign the needed logic processor variables to it.
Select the Control OPC Item Path parameter in the Object Properties view and click
the “…” button to launch the PLC OPC Item Path dialog, see Figure 4.12-1.
SAB600_SC_PLC_OPC_Item_Path.png
Figure 4.12-1 Assigning OPC Item Path to SEQGGIO1.Str data object
Set the **.(SequenceObject).SeqStartStopControl logic processor variable as the
control item path. Similarly, assign **.(SequenceObject).SeqStartStopControl
as the OPC item for State OPC item path.
2.
Select Logic Processor_IED > Sequence logical device > SEQGGIO1 > St data
object and assign the needed logic processor variables to it.