SAB600_SC_Cross_References.png
Figure 4.11-1 Launching the Cross References tool
If the variables defined from Logic Processor are not shown, click Import and select
the “ProjectName”.Device.Application.xml file (for example, SequentialControl-
Setup.Device.Application.xml).
2.
Assign the breaker (*CSWI*) data attributes to a corresponding SwitchObject
variable. The array indices available with the Switches variable from the logic pro-
cessor indicate the breaker object indentification. For example, Switches[1].Status
refers to status indication for the breaker mapped to SwitchObject in Switches[1].
3.
To map a data attribute from COM600 communication structure to a variable from
the Logic Processor, select the data object from the communication structure view
and drag and drop it to the corresponding sequence variable to be mapped.
4.
Edit the data object manually to map the right data attribute by selecting the cell in
the OPC Server Path column and editing the attribute. For any sequence object from
the logic processor, the breaker data attributes needed to be mapped are shown in
Table 4.11-1.
5.
Finish mapping the CSWI data attributes to corresponding switch select/operate
controls for all the indices for the Switches array.
6.
Click Apply and close the Cross References tool.
Table 4.11-1 Breaker data attributes mapping to Logic Processor Sequence Object
Direction
Data Variable of a Sequence Object
Breaker Data Attributes
->
**.SwitchArray[Index].SwStatus[1]
*CSWI*/Pos/stVal
38
1MRS755001
COM600 series 5.1
Sequence Control Configuration Manual