Delta (DEL)
4.2.12.
DEL represents DMCD M_ME_NA_1, M_ME_TA_1, M_ME_TD_1, M_ME_NB_1,
M_ME_TB_1, M_ME_NC_1, M_ME_TC_1, M_ME_TF_1.
OPC data types
Protocol informa-
tion element
Mandat-
ory/Optional
Value/ Value
range
Type
Name
VT_R4
VT_I4
VT_DATE
SVA, NVA
OV, BL, SB, NT, IV
CP24Time2A
M
M
M
AnalogueValue
Quality
TimeStamp
phsAB. cVal.mag t
phsAB.q
phsAB.t
VT_R4
VT_I4
VT_DATE
SVA, NVA
OV, BL, SB, NT, IV
CP24Time2A
M
M
M
AnalogueValue
Quality
TimeStamp
phsBC.cVal.mag q
phsBC.q
phsBC.t
VT_R4
VT_I4
VT_DATE
SVA, NVA
OV, BL, SB, NT, IV
CP24Time2A
M
M
M
AnalogueValue
Quality
TimeStamp
phsCA.cVal.mag q
phsCA.q
phsCA.t
Controllable single point (SPC)
4.2.13.
SPC represents DMCD C_SC_NA_1, C_DC_NA_1, M_SP_NA_1, M_SP_TA_1,
M_SP_TB_1, M_DP_NA_1, M_DP_TA_1, M_DP_TB_1.
OPC data types
Protocol informa-
tion element
Mandat-
ory/Optional
Value/ Value
range
Type
Name
VT_BOOL
SCO
M
SPI
ctlVal
VT_BOOL
SPI
M
FALSE | TRUE
stVal
VT_I4
BL, SB, NT, IV
M
Quality
q
VT_DATE
CP24Time2A
M
TimeStamp
t
VT_BSTR
O
Text
Description
d
Controllable double point (DPC)
4.2.14.
DPC represents DMCD C_SC_NA_1, C_DC_NA_1, M_SP_NA_1, M_SP_TA_1,
M_SP_TB_1, M_DP_NA_1, M_DP_TA_1, M_DP_TB_1.
OPC data types
Protocol informa-
tion element
Mandat-
ory/Optional
Value/ Value
range
Type
Name
VT_BOOL
SCO
O
FALSE | TRUE
SPI
ctlOperOn
VT_BOOL
SCO
O
FALSE | TRUE
ctlOperOff