Binary counter reading (BCR)
5.2.8.
OPC data types
DNP data object
field
Mandat-
ory/Optional
Value/Value range
Type
Name
VT_I4
Value | Frozen
value | Current
value
M
INTEGER
actVal
VT_14
Config
O
Integer
siUnit
VT_14
Config
O
Integer
multiplier
VT_BSTR
Config
O
Integer
unit
VT_I4
DNP status
M
Quality
q
VT_DATE
<server provided if
none> | Time of
occurrence | MSCE
M
TimeStamp
t
Device name plate (DPL)
5.2.9.
OPC data types
DNP data object
field
Mandat-
ory/Optional
Value/Value range
Type
Name
VT_BSTR
-
M
VisibleString
vendor
VT_BSTR
-
O
VisibleString
hwRevision
VT_BSTR
-
O
VisibleString
swRevision
VT_BSTR
-
O
VisibleString
serNum
VT_BSTR
-
O
VisibleString
location
Logical node name plate (LPL)
5.2.10.
OPC data types
DNP information
element
Mandat-
ory/Optional
Value/Value range
Type
Name
VT_BSTR
Separate signal
M
VisibleString
vendor
VT_BSTR
Separate signal
M
VisibleString
swRev
VT_BSTR
Separate signal
M
VisibleString
d
105
COM600 series 5.0
1MRS758690
Master Protocols (Ethernet) and Applications Technical Refer-
ence Manual