M_EP_TF_1
:=Packed output circuit information of protection
equipment with time tag CP56Time2a
<40>
Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>,
<19> or of the set <30> - <40> are used.
Process information in control direction (station-specific parameter)
C_SC_NA_1
:=Single command
<45>
C_DC_NA_1
:=Double command
<46>
C_RC_NA_1
:=Regulating step command
<47>
C_SE_NA_1
:=Set point command, normalized value
<48>
C_SC_NB_1
:=Set point command, scaled value
<49>
C_SC_NC_1
:=Set point command, short float point value
<50>
C_BO_NA_1
:=Bitstring of 32 bit
<51>
C_SC_TA_1
:=Single command with time tag CP56Time2a
<58>
C_DC_TA_1
:=Double command with time tag CP56Time2a
<59>
C_RC_TA_1
:=Regulating step command with time tag
CP56Time2a
<60>
C_SE_TA_1
:=Set point command, normalized value with time tag
CP56Time2a
<61>
C_SE_TB_1
:=Set point command, scaled value with time tag
CP56Time2a
<62>
C_SE_TC_1
:=Set point command, short floating point value with
time tag CP56Time2a
<63>
C_BO_TA_1
:=Bitstring of 32 bit with time tag CP56Time2a
<64>
Either the ASDUs of the set <45> - <51> or of the set <58> - <64> are used.
System information in monitor direction (station-specific parameter)
M _EI_NA_1
:=End of initialization
<70>