Table 3.2.2-1 IEC 61850 quality
Bit
M/O/C
Value/Value
range
Type
Name
0-1
M
good (0) | invalid
(1) | reserved (2)
| questionable (3)
2bit
validity
2
M
FALSE (0) |
TRUE (1)
1bit
overflow
3
M
FALSE (0) |
TRUE (1)
1bit
outOfRange
4
M
FALSE (0) |
TRUE (1)
1bit
badReference
5
M
FALSE (0) |
TRUE (1)
1bit
oscillatory
6
M
FALSE (0) |
TRUE (1)
1bit
failure
7
M
FALSE (0) |
TRUE (1)
1bit
oldData
8
M
FALSE (0) |
TRUE (1)
1bit
inconsistent
9
M
FALSE (0) |
TRUE (1)
1bit
inaccurate
10-11
M
process (0) | sub-
stituted (1)
2bit
source
12
M
FALSE (0) |
TRUE (1)
1bit
test
13
M
FALSE (0) |
TRUE (1)
1bit
operatorBlocked
Mapping quality value to OPC
3.2.3.
The value of validity is presented as the value of the quality attribute. The other values
are presented as OPC properties of the quality in the OPC namespace.
Table 3.2.3-1 Mapping quality value to OPC
OPC Data Type
M/O/C
Value/ Value
range
Type
Name
VT_I4
M
good (0) | invalid
(1) | reserved (2)
| questionable (3)
Validity
VT_I4
M
DetailedQuality
DetailQuality
VT_I4
M
process (0) | sub-
stituted (1)
Source
25
COM600 series 5.0
1MRS758690
Master Protocols (Ethernet) and Applications Technical Refer-