24
…7.2
Control Page
Return to the top of the
Control Page
or advance to the next
page.
…7
CONTROL LEVEL
Set
Point
Prop.
Band
500
600
400
Time
Offset = 50%
Set
Point
Prop.
Band
500
Time
Offset = 0%
PV
PV
300
o r
SEt
OFFSEt
50.0
Mr–AdJ
YES
PrOGrAM
PrOFLE
POINtS
OFF
50.0
Integral
Action
Time
Set
Int. Action
Time Off
OFF
APPb
M.r ESEt
INtGrL
dErIV
1.0
t–untS
SECS
Integral
Action
Time
Set
Time Units
Time units for the integral and derivative action times (see
below) can be set to minutes
MINS
or seconds
SECS
.
Integral Action Time
Set the required time between 1 and 7200 in 1 second
increments (0.1 and 120 minutes in 0.1 minute
increments).
OFF
is displayed in place of 7201 (120.1)
Note. An
Integral Action Time
must be set when the
Control
Type
is set to
bNdLSS
.
Manual Reset
Manual reset is only operable with
Integral Action Time
set to
OFF
. Set the required proportional band offset between 0.0
and 100.0% of the display (engineering) span in 0.1%
increments.
Derivative Action Time
Set the required time between 0.0 and 999.9 in 0.1 second
increments (0.1 and 16.67 minutes in 0.01 minute
increments).
OFF
is displayed in place of zero.
Approach Band
Set the required value between 0.1 and 3.0 in 0.1
increments. (Set 1.0 initially.)
Manual Reset Adjust Enable
This display and adjustment in the
Operating Page
can be
enabled or disabled.
Select
YES
to enable or
no
to disable.
Control Algorithm Offset
This frame is only applicable if
Integral Action Time
is set,
(i.e. is not set to
OFF
). Set the required offset, either 0.0 or
50.0%.