![ABB C300 Скачать руководство пользователя страница 12](http://html.mh-extra.com/html/abb/c300/c300_operating-manual_3032012.webp)
10
…5
OPERATING LEVEL
Manual Reset (Heat)
Manual Reset (Cool)
Control Set Point
The set point in use is displayed (Local, Remote or Dual).
If the Local or Dual set point is displayed it can be adjusted
using the
and
switches, providing
Set Point Adjust
Enable
is set to
YES
– see
Section 4.2 of the Programming
Guide,
Set Points Page
.
Percentage Output (Heat, Cool and PID)
To adjust the output value manually: select Manual control
mode using the
switch ('M' l.e.d. is illuminated) and
then use the
and
switches to set the value required
(between 0 and 100%).
Cool Output
This frame is not
displayed if the P.I.D.
output is
above
the
Crossover Value
.
Heat Output
This frame is not
displayed if the P.I.D.
output is
below
the
Crossover Value
.
PID Output
100.3
110.5
100.3
OP 50.0
100.3
oh 50.0
100.3
oc 50.0
100.3
rc 50.0
100.3
rh 50.0
100.3
dEG F
rAtIO
1.000
bIAS
0.0
LOCAL
110.5
Manual Reset, Heat and Cool (0 to 100%).
This frame is not displayed if an
Integral Action Time
is set
or
Manual Reset Adjust Enable
is set to
OFF
– see Section
7.2,
Control Page
.
Use the
and
switches to set a value which
eliminates any offset from the set point.
Temperature Units
This frame is not displayed if the
Display Units
parameter is
set to
NONE
– see
Section 4.8 of the Programming Guide
Set Up Display Page
.
For
Set Point Type Selection
,
Remote Set Point Ratio
and
Remote Set Point Bias
settings, refer to page 8.
5.2.3
Heat/Cool Control