ABB BL-1 Скачать руководство пользователя страница 5

I.L. 41-553.1G

edge and a pinion attached to the scale pointer.
This serves to expand the scales and permit in-

-

creased accuracy of setting.

Stationary break contacts can be provided

when required. These are similar to the make con-
tacts and are mounted on a second rotatable plate
in front of the plate which supports the make con-
tacts. This plate is held in position by spring
pressure, but can be moved to any desired position
with reference to the make contacts. A scale on the
supporting plate for the make contacts is used in
locating the break contacts at a definite position.

Rotation of the make contacts by means of the

scale pointer does not change the spacing between
the make and the break contacts.

INSTANTANEOUS UNIT

This is a small solenoid type unit. A cylindrical

plunger moves up and down on a vertical guide
rod in the center of the solenoid coil. This guide
rod is fastened to the stationary core which in turn

screws into the element frame. A silver disc is

fastened to the moving plunger thru a helical
spring. When the coil is energized, the plunger
moves upward carrying the silver disc which
bridges three conical shaped stationary contacts.
After the contacts close the plunger moves slightly
farther before seating against the stationary core.

This assures positive contact pressure.

A Micarta disc on a threaded bushing is

assembled on the lower portion of the guide rod

and is locked in place by a nut. Its position deter-

mines the de-energized position of the plunger and
therefore the pickup current of the element, as in-

dicated by the graduated scale beside the disc.

OPERATION INDICATOR

The operation indicator is a small solenoid coil

connected in the trip circuit. When the coil is

energized, a spring-restrained armature releases

the white target which falls by gravity to indicate
the completion of the trip circuit. The indicator is
reset from outside the case by a push rod in the
cover or cover stud.

CONTACTOR SWITCH

The dc contactor switch in the relay is a small

solenoid type switch. A cylindrical plunger with a

silver disc mounted on its lower end moves in the
core of the solenoid. As the plunger travels up-
ward, the disc bridges three stationary contacts.
The coil is in series with the main contacts of the
relay and with the trip coil of the breaker. When
the relay contacts close, the coil becomes energized

and closes the switch contacts. This shunts the

main relay contacts, thereby relieving them of the

duty of carrying tripping current. These contacts

remain closed until the trip circuit is opened by the

auxiliary switch on the breaker.

CHARACTERISTICS

The type BL-1 relay is designed for use in

applications where the current transformer ratio is
such that with 100 percent of full load on the
protected machine the relay will receive a current
within the limits of 2.5 to 5.0 amperes. For full
load currents within the range, the relay can be set

to operate in accordance with the characteristic
curves shown in Figs. 5 and 6. Note that there are
three initial current conditions shown in each

figure: O%,  70%,  and 100% of pointer setting. The

curves are based upon having the initial current

maintained long enough for the moving contact to

stop moving. Then the current is increased to some
percent of pointer setting to obtain the operating
time.

Since an overload might occur at or shortly

after the time a motor is started, or after a motor
has reached a constant temperature rise while
carrying less than full load, Figs. 5 and 6 show how
the operating time will be affected for a zero initial
load and for a 70 percent initial load. As would be
expected, the operating time is somewhat longer
for these conditions, but the protected motor could

carry the overload longer before reaching a
dangerous temperature.

It will be observed that the curves for the 2.5

and the 3.5 ampere settings diverge somewhat as

the overload increases. The amount of divergence
will not seriously affect any application of the
relay. For full load current settings greater than
2.5 amperes but less than 3.5 amperes, the
operating time at any of the higher values of
overload can readily be obtained by interpolation.

5

Courtesy of NationalSwitchgear.com

Содержание BL-1

Страница 1: ...plications However the drop across a portion of the protected circuit such as the interpole field win ding of a machine sometimes can be utilized as a source of energy for the relay CONSTRUCTION AND OPERATION The single element type BL 1 relay consists of a heater unit an instantaneous overcurrent unit 0 two operation indicators and a contactor switch Figures 1 3 The double element type BL 1 relay...

Страница 2: ...Fig 1 Type BL 1 Single Unit Relay without case Front View 2 ...

Страница 3: ...I L 41 553 1G Fig 2 Type BL 1 Double Unit Relay without case Front View 3 Courtesy of NationalSwitchgear com ...

Страница 4: ... currents of short duration The reactor should be removed from the circuit for dc application This is readily accomplished by removing the heavier lead from the two left hand terminals of each thermal unit enclosure of the internal spring will cause it to res pond more slowly than the external spring and a temporary change in contact position would result from a large and rapid change in ambient t...

Страница 5: ... is a small solenoid type switch A cylindrical plunger with a silver disc mounted on its lower end moves in the core of the solenoid As the plunger travels up ward the disc bridges three stationary contacts The coil is in series with the main contacts of the relay and with the trip coil of the breaker When the relay contacts close the coil becomes energized and closes the switch contacts This shun...

Страница 6: ...TACT REACHES FINAL POSITION FOR INITIAL STEADY LOAD INDICATED BELOW ZERO CURRENT INTERNAL TEMP AT APPROX AMBIENT TEMP 70 OF 3 5 AMPS 100 OF 3 5 AMPS V 1 5 1 1 1 1 l i I I I I 1 1 HT V 1 1 1 I I V i T u I I i I l I I I 1 r I I 1 1 X m 9 v 8 V XT T 7 m 6 V p a 5 i m A 1 m X 4 X p jz H t PI A 3 T X7 i V x x 2 I m r r f i 1 i s u s I 1 1 1 1 L 1 i I I I I I I i K J 1 i I i I I I U 1 I I i I k I i I 1 ...

Страница 7: ...OAD APPLIED AFTER MOVING CONTACT REACHES FINAL POSITION FOR INITIAL STEADY LOAD INDICATED BELOW ZERO CURRENT INTERNAL TEMP AT APPROX AMBIENT TEMP 70 OF 5 AMPS 100 OF 5 AMPS l T T i i i V I M V I 1 v J jOk X 9 8 PI 7 J 6 I z4 v 5 7 5 fK 5 V 4 I X 3 Tx X X I iz i ri w i ES i 2 v r 7 i_L l v L C 1 n f LLU i A 1 1 1 1 I 093 MIN AT 1000 L s i i 1 100 200 300 400 500 600 700 800 900 1000 PERCENT OF POIN...

Страница 8: ... I I i I 1 X T j yY T V 4 9 rr 8 is 3 FOR 2 75 AMP SETTING FOR 3 75 AMP SETTING WHEN STARTING FROM 100J OF FULL LOAD CURRENT 6 51 5 5 Y rt Y 5 Y 5r V L 5 1 X Y T j 3 r i K IT 2 1 I i l J i 075 MIN AT 1000J 1 r 100 200 300 400 500 600 700 800 900 1000 PERCENT OF FULL LOAD CURRENT 396063 Curve Fig 7 Current T ime Curves for Special Applications of the Type BL 1 Relay covering Range of F ull Load Cur...

Страница 9: ...pe BL 1 Relay Covering Range of Fufl Load Currents from 4 0 to 5 0 Amperes Contact Settings Determined by Test for 15 Minute Delay with 125 Load Occurring after Moving Contact reaches Final Position for Steady Full Load Shorting Link Closed 9 Courtesy of NationalSwitchgear com ...

Страница 10: ...Fig 9 Contact Opening and Reset Time Curves for the Type BL 1 Reioy for Fult Load Settings of 2 5 to 3 5 Amperes os marked on Dial Shorting Link Open 10 Courtesy of NationalSwitchgear com ...

Страница 11: ...L 41 553 1G Contact Opening and Reset Time Curves for the Type BL 1 Relay for Full Load Settings of 3 75 to 5 0 Amperes as marked on Dial Shorting Link Closed Fig 10 11 Courtesy of NationalSwitchgear com ...

Страница 12: ... ampere steps and when the scale pointer is set to one of the indicated current values the relay contacts will close in ap proximately 60 minutes if the current increases to 125 percent of the full load value after the full load current has been flowing long enough for the temperature rise to reach a constant value These curves represent the primary performance re quirements of the type BL 1 relay...

Страница 13: ...of current that will ultimately close the relay contacts but variables such as friction and dis crepancies in calibration prevent precise location of the asymptotic value However after making some allowance for such variables a value of 118 of full load current can be considered as the max imum current that will not produce eventual clos ing of the relay contacts when settings are made as describe...

Страница 14: ...supplied in the type BL 1 relay will pick up at 1 0 ampere direct current For detail information on the FT case refer to I L 41 076 SETTINGS CONTACT RATINGS There are two settings to be made on the relay They are as follows Control Capacity Will Break Control Voltage In Amperes Will Close Unit 1 INSTANTANEOUS UNIT Set the element for a pick up current slightly above the maximum current which the a...

Страница 15: ...lower right posi tion Close switch S1 and pass sufficient dc current through the trip circuit to close the contacts of the ICS This value of current should not be greater than the particular ICS nameplate rating The in dicator target should drop freely Repeat above except to pass 85 of ICS nameplate rating current Contacts should not pick up and target should not drop Open switch S1 when checking ...

Страница 16: ...roximately 16 CONTACTOR SWITCH Adjust the stationary core of the switch for a clearance between the stationary core and the moving core of l 64 when the switch is picked up This can be done by turning the relay up side down or by disconnecting the switch and turning it up side down Then screw up the core screw until the moving core starts rotating Now back off the core screw until the moving core ...

Страница 17: ...minimize factors which would introduce calibra tion errors The test current should be interrupted as soon as the contacts close in order to avoid possible damage to the heaters particularly when testing at high values of overload RENEWAL PARTS Repair work can be done most satisfactorily at the factory However interchangeable parts can be furnished to the customers who are equipped for doing repair...

Страница 18: ... 14 30 _ 5 375 36 53 4 0I6 397 250 _ 6 35 0 f 1 031 f 1 031 4 1 031 t 1 031 H 26 19 26 19 26 19 26 19 1 190 32 SCREW 375 1 344 SPACERS FOR 34 14 THIN PANELS 9 53 R PANEL CASE 1 r A 5 16 18 SCREW FOR THICK PANELS USE 5 16 18 STUDS INTERNAL EXTERNAL TOOTHED WASHERS 190 32 SCREW FOR THICK PANELS USE 190 32 STUDS 594 15 09 1 0 25 4 Li nt 5A 77 3 9 i 1 813 i 2 0 i 46 05 i 50 8 i IOV 2 4 6 8 1 V 516 13 ...

Отзывы: