ABB BL-1 Скачать руководство пользователя страница 15

TYPE BL-1 RELAY

LL. 41-553.2B

The vertical edge setting may be set for a larger
contact gap but should not be set for more than six
minor divisions if the break contacts are to be in a
closed position at full load.

External diagram in Fig. 9 show several com-

binations for applying these units.

ADJUSTMENT & MAINTENANCE

The proper adjustments to insure correct

operation of this relay have been made at the fac-

tory. Upon receipt of the relay no customer ad-

justments, other than those covered under

“SETTINGS” should be required.

ROUTINE MAINTENANCE

All relays should be inspected and checked

once a year or at other time intervals as dictated by
experience to assure proper operation. Generally a
visual inspection should call attention to any
noticeable changes. A minimum suggested check
on the relay system is to close the contacts manual-
ly to assure that the breaker trips and the target

drops. If an additional time check is desired, pass
test current through the relay and check the time
of operation.

All contacts should be periodically cleaned. A

contact burnisher #182A836HOl is recommended
for this purpose. The use of abrasive material for

cleaning contacts is not recommended, because of
the danger of embedding small particles in the face

of the soft silver and thus impairing the contact.

ACCEPTANCE CHECK 

AND

CALIBRATION

ICS ACCEPTANCE CHECK

Refer to test diagram shown in Fig. IO.

Connect an adjustable dc current source to relay
terminal 4 as shown with a jumper type connection
made inside the relay. Connect the jumper to the
right hand (facing the front of the relay) stationary
contact of the ICS located in the lower right posi-
tion.

Close switch S1 and pass sufficient dc current

through the trip circuit to close the contacts of the

ICS. This value of current should not be greater
than the particular ICS nameplate rating. The in-

dicator target should drop freely.

Repeat above except to pass 85% of ICS

nameplate rating current. Contacts should not
pick up and target should not drop. Open switch
S1 when checking is completed.

ICS

 CALIBRATION

Use the following procedure for calibrating the

relay if the relay has been taken apart for repairs
or the adjustment have been disturbed. This
procedure should not be used unless it is apparent

that the relay is not in proper working order. (See

“Acceptance Check”).

Initially adjust unit on the pedestal so that ar-

mature lingers do not touch the yoke in the reset
position. This can be done by loosening the moun-
ting screw in the molded pedestal and moving the

ICS in the downward position.

1. Contact Wipe: Adjust the stationary con-

tacts so that both stationary contacts make
with the moving contacts simultaneously

and wipe l/64”  to 3/64”  when the armature
is aganist the core.

For double trip type units, adjust the third

contact so that it makes with its stationary
contacts at the same time as the two main
contacts or up to 1/64”  ahead.

2. Target: Manually raise the moving contacts

and check to see that the target drops at the
same time the contacts make or up to  1 / 16"
ahead. The cover may be removed and the
tab holding the target reformed slightly if
necessary. However, care should be exer-
cised so that the target will not drop due to a
slight jar.

3. Pickup: Unit should pickup at 98% of rating

and not pickup at 85% or rating. If
necessary the cover leaf springs may be ad-

justed. To lower the pickup current, use a

tweezer or similar tool and squeeze each

15

Courtesy of NationalSwitchgear.com

Содержание BL-1

Страница 1: ...plications However the drop across a portion of the protected circuit such as the interpole field win ding of a machine sometimes can be utilized as a source of energy for the relay CONSTRUCTION AND OPERATION The single element type BL 1 relay consists of a heater unit an instantaneous overcurrent unit 0 two operation indicators and a contactor switch Figures 1 3 The double element type BL 1 relay...

Страница 2: ...Fig 1 Type BL 1 Single Unit Relay without case Front View 2 ...

Страница 3: ...I L 41 553 1G Fig 2 Type BL 1 Double Unit Relay without case Front View 3 Courtesy of NationalSwitchgear com ...

Страница 4: ... currents of short duration The reactor should be removed from the circuit for dc application This is readily accomplished by removing the heavier lead from the two left hand terminals of each thermal unit enclosure of the internal spring will cause it to res pond more slowly than the external spring and a temporary change in contact position would result from a large and rapid change in ambient t...

Страница 5: ... is a small solenoid type switch A cylindrical plunger with a silver disc mounted on its lower end moves in the core of the solenoid As the plunger travels up ward the disc bridges three stationary contacts The coil is in series with the main contacts of the relay and with the trip coil of the breaker When the relay contacts close the coil becomes energized and closes the switch contacts This shun...

Страница 6: ...TACT REACHES FINAL POSITION FOR INITIAL STEADY LOAD INDICATED BELOW ZERO CURRENT INTERNAL TEMP AT APPROX AMBIENT TEMP 70 OF 3 5 AMPS 100 OF 3 5 AMPS V 1 5 1 1 1 1 l i I I I I 1 1 HT V 1 1 1 I I V i T u I I i I l I I I 1 r I I 1 1 X m 9 v 8 V XT T 7 m 6 V p a 5 i m A 1 m X 4 X p jz H t PI A 3 T X7 i V x x 2 I m r r f i 1 i s u s I 1 1 1 1 L 1 i I I I I I I i K J 1 i I i I I I U 1 I I i I k I i I 1 ...

Страница 7: ...OAD APPLIED AFTER MOVING CONTACT REACHES FINAL POSITION FOR INITIAL STEADY LOAD INDICATED BELOW ZERO CURRENT INTERNAL TEMP AT APPROX AMBIENT TEMP 70 OF 5 AMPS 100 OF 5 AMPS l T T i i i V I M V I 1 v J jOk X 9 8 PI 7 J 6 I z4 v 5 7 5 fK 5 V 4 I X 3 Tx X X I iz i ri w i ES i 2 v r 7 i_L l v L C 1 n f LLU i A 1 1 1 1 I 093 MIN AT 1000 L s i i 1 100 200 300 400 500 600 700 800 900 1000 PERCENT OF POIN...

Страница 8: ... I I i I 1 X T j yY T V 4 9 rr 8 is 3 FOR 2 75 AMP SETTING FOR 3 75 AMP SETTING WHEN STARTING FROM 100J OF FULL LOAD CURRENT 6 51 5 5 Y rt Y 5 Y 5r V L 5 1 X Y T j 3 r i K IT 2 1 I i l J i 075 MIN AT 1000J 1 r 100 200 300 400 500 600 700 800 900 1000 PERCENT OF FULL LOAD CURRENT 396063 Curve Fig 7 Current T ime Curves for Special Applications of the Type BL 1 Relay covering Range of F ull Load Cur...

Страница 9: ...pe BL 1 Relay Covering Range of Fufl Load Currents from 4 0 to 5 0 Amperes Contact Settings Determined by Test for 15 Minute Delay with 125 Load Occurring after Moving Contact reaches Final Position for Steady Full Load Shorting Link Closed 9 Courtesy of NationalSwitchgear com ...

Страница 10: ...Fig 9 Contact Opening and Reset Time Curves for the Type BL 1 Reioy for Fult Load Settings of 2 5 to 3 5 Amperes os marked on Dial Shorting Link Open 10 Courtesy of NationalSwitchgear com ...

Страница 11: ...L 41 553 1G Contact Opening and Reset Time Curves for the Type BL 1 Relay for Full Load Settings of 3 75 to 5 0 Amperes as marked on Dial Shorting Link Closed Fig 10 11 Courtesy of NationalSwitchgear com ...

Страница 12: ... ampere steps and when the scale pointer is set to one of the indicated current values the relay contacts will close in ap proximately 60 minutes if the current increases to 125 percent of the full load value after the full load current has been flowing long enough for the temperature rise to reach a constant value These curves represent the primary performance re quirements of the type BL 1 relay...

Страница 13: ...of current that will ultimately close the relay contacts but variables such as friction and dis crepancies in calibration prevent precise location of the asymptotic value However after making some allowance for such variables a value of 118 of full load current can be considered as the max imum current that will not produce eventual clos ing of the relay contacts when settings are made as describe...

Страница 14: ...supplied in the type BL 1 relay will pick up at 1 0 ampere direct current For detail information on the FT case refer to I L 41 076 SETTINGS CONTACT RATINGS There are two settings to be made on the relay They are as follows Control Capacity Will Break Control Voltage In Amperes Will Close Unit 1 INSTANTANEOUS UNIT Set the element for a pick up current slightly above the maximum current which the a...

Страница 15: ...lower right posi tion Close switch S1 and pass sufficient dc current through the trip circuit to close the contacts of the ICS This value of current should not be greater than the particular ICS nameplate rating The in dicator target should drop freely Repeat above except to pass 85 of ICS nameplate rating current Contacts should not pick up and target should not drop Open switch S1 when checking ...

Страница 16: ...roximately 16 CONTACTOR SWITCH Adjust the stationary core of the switch for a clearance between the stationary core and the moving core of l 64 when the switch is picked up This can be done by turning the relay up side down or by disconnecting the switch and turning it up side down Then screw up the core screw until the moving core starts rotating Now back off the core screw until the moving core ...

Страница 17: ...minimize factors which would introduce calibra tion errors The test current should be interrupted as soon as the contacts close in order to avoid possible damage to the heaters particularly when testing at high values of overload RENEWAL PARTS Repair work can be done most satisfactorily at the factory However interchangeable parts can be furnished to the customers who are equipped for doing repair...

Страница 18: ... 14 30 _ 5 375 36 53 4 0I6 397 250 _ 6 35 0 f 1 031 f 1 031 4 1 031 t 1 031 H 26 19 26 19 26 19 26 19 1 190 32 SCREW 375 1 344 SPACERS FOR 34 14 THIN PANELS 9 53 R PANEL CASE 1 r A 5 16 18 SCREW FOR THICK PANELS USE 5 16 18 STUDS INTERNAL EXTERNAL TOOTHED WASHERS 190 32 SCREW FOR THICK PANELS USE 190 32 STUDS 594 15 09 1 0 25 4 Li nt 5A 77 3 9 i 1 813 i 2 0 i 46 05 i 50 8 i IOV 2 4 6 8 1 V 516 13 ...

Отзывы: