ABB BL-1 Скачать руководство пользователя страница 16

break contacts, and when closer settings are
desired they should be made by test.

ADJUSTMENTS AND MAINTENANCE

The proper adjustments to insure correct

operation of this relay have been made at the fac-
tory and should not be disturbed after receipt by
the customer. Contact or pickup settings must be
made as required by the application, but alteration

of assembly adjustments should be avoided. If the
adjustments have been changed, if the relay has
been taken apart for repairs, or if it is desired to
check the adjustments at regular maintenance
periods, instructions below should be followed.

All contacts should be cleaned periodically. A

contact burnisher S#182A836HOl  is recommend-
ed for this purpose. The use of abrasive material

for cleaning contacts is not recommended, because

of the danger of embedding small particles in the
face of the soft silver and thus impairing the con-
tact.

INSTANTANEOUS UNIT

Remove the plunger core and see that the top

of the plunger is clean. Reassemble the plunger,
and adjust the position of the core screw so that
when the contacts are closed the plunger butts
against the stop with the spring half compressed.
With a l/32 inch contact separation, the contacts
should pick-up at 6 amperes, 60 cycles. If the

plunger does not pickup and seal in at this current,
adjust the core screw so that it will and yet have
sufficient compression of the spring to prevent
sticking. Test for sticking after 50 amperes has
been passed through the coil.

OPERATION INDICATOR

Adjust the indicator to operate at 1.0 ampere

direct current gradually applied by loosening the
two screws on the under side of the assembly, and
moving the bracket forward or backward. If the
two helical springs which reset the armature are
replaced by new springs they should be weakened
slightly by stretching to obtain

calibration. The coil resistance is
0.16 ohm.

the 1 ampere

approximately

1 6

CONTACTOR SWITCH

Adjust the stationary core of the switch for a

clearance between the stationary core and the
moving core of l/64”  when the switch is picked
up. This can be done by turning the relay up-side-
down or by disconnecting the switch and turning it
up-side-down. Then screw up the core screw until
the moving core starts rotating. Now, back off the
core screw until the moving core stops rotating.

This indicates the points where the play in the
assembly is taken up, and where the moving core

just separates from the stationary core screw. Back

off the core screw approximately one turn and lock
in place. This prevents the moving core from strik-
ing and sticking to the stationary core because of
residual magnetism. Adjust the contact clearance
for 3/32” by means of the two small nuts on either

side 

of the the Micarta disc. The switch should

pick up at 2 ampere dc. Test for sticking after 30
amperes have been passed through the coil.

HEATER UNIT

The assembly and adjustment of the thermal

unit requires alignment fixtures and other special
tools, as well as special test equipment for locating
the position of the compensating spring assembly

on the shaft and determining the calibration
points. Any dismantling or alteration of the ad-

justments should be avoided, as this may result in

excessive bearing friction or calibration errors.

However, the construction and overload capacity

of the thermal unit is such that very little
maintenance should be required.

The resistance of the heater and instantaneous

unit, measured at the case terminals, should be
0.25 ohm when the shorting link is open and 0.13
ohm when the link is closed.

The moving contact should rotate without

noticeable friction, and when displaced manually
and released it should return to its original posi-
tion. The shaft should have about 0.010 inch end
play.

If the calibration of the thermal unit is to be

checked at one or more points, the precautions
mentioned in previous sections should be observed.
Testing should be done with the relay in its case

Courtesy of NationalSwitchgear.com

Содержание BL-1

Страница 1: ...plications However the drop across a portion of the protected circuit such as the interpole field win ding of a machine sometimes can be utilized as a source of energy for the relay CONSTRUCTION AND OPERATION The single element type BL 1 relay consists of a heater unit an instantaneous overcurrent unit 0 two operation indicators and a contactor switch Figures 1 3 The double element type BL 1 relay...

Страница 2: ...Fig 1 Type BL 1 Single Unit Relay without case Front View 2 ...

Страница 3: ...I L 41 553 1G Fig 2 Type BL 1 Double Unit Relay without case Front View 3 Courtesy of NationalSwitchgear com ...

Страница 4: ... currents of short duration The reactor should be removed from the circuit for dc application This is readily accomplished by removing the heavier lead from the two left hand terminals of each thermal unit enclosure of the internal spring will cause it to res pond more slowly than the external spring and a temporary change in contact position would result from a large and rapid change in ambient t...

Страница 5: ... is a small solenoid type switch A cylindrical plunger with a silver disc mounted on its lower end moves in the core of the solenoid As the plunger travels up ward the disc bridges three stationary contacts The coil is in series with the main contacts of the relay and with the trip coil of the breaker When the relay contacts close the coil becomes energized and closes the switch contacts This shun...

Страница 6: ...TACT REACHES FINAL POSITION FOR INITIAL STEADY LOAD INDICATED BELOW ZERO CURRENT INTERNAL TEMP AT APPROX AMBIENT TEMP 70 OF 3 5 AMPS 100 OF 3 5 AMPS V 1 5 1 1 1 1 l i I I I I 1 1 HT V 1 1 1 I I V i T u I I i I l I I I 1 r I I 1 1 X m 9 v 8 V XT T 7 m 6 V p a 5 i m A 1 m X 4 X p jz H t PI A 3 T X7 i V x x 2 I m r r f i 1 i s u s I 1 1 1 1 L 1 i I I I I I I i K J 1 i I i I I I U 1 I I i I k I i I 1 ...

Страница 7: ...OAD APPLIED AFTER MOVING CONTACT REACHES FINAL POSITION FOR INITIAL STEADY LOAD INDICATED BELOW ZERO CURRENT INTERNAL TEMP AT APPROX AMBIENT TEMP 70 OF 5 AMPS 100 OF 5 AMPS l T T i i i V I M V I 1 v J jOk X 9 8 PI 7 J 6 I z4 v 5 7 5 fK 5 V 4 I X 3 Tx X X I iz i ri w i ES i 2 v r 7 i_L l v L C 1 n f LLU i A 1 1 1 1 I 093 MIN AT 1000 L s i i 1 100 200 300 400 500 600 700 800 900 1000 PERCENT OF POIN...

Страница 8: ... I I i I 1 X T j yY T V 4 9 rr 8 is 3 FOR 2 75 AMP SETTING FOR 3 75 AMP SETTING WHEN STARTING FROM 100J OF FULL LOAD CURRENT 6 51 5 5 Y rt Y 5 Y 5r V L 5 1 X Y T j 3 r i K IT 2 1 I i l J i 075 MIN AT 1000J 1 r 100 200 300 400 500 600 700 800 900 1000 PERCENT OF FULL LOAD CURRENT 396063 Curve Fig 7 Current T ime Curves for Special Applications of the Type BL 1 Relay covering Range of F ull Load Cur...

Страница 9: ...pe BL 1 Relay Covering Range of Fufl Load Currents from 4 0 to 5 0 Amperes Contact Settings Determined by Test for 15 Minute Delay with 125 Load Occurring after Moving Contact reaches Final Position for Steady Full Load Shorting Link Closed 9 Courtesy of NationalSwitchgear com ...

Страница 10: ...Fig 9 Contact Opening and Reset Time Curves for the Type BL 1 Reioy for Fult Load Settings of 2 5 to 3 5 Amperes os marked on Dial Shorting Link Open 10 Courtesy of NationalSwitchgear com ...

Страница 11: ...L 41 553 1G Contact Opening and Reset Time Curves for the Type BL 1 Relay for Full Load Settings of 3 75 to 5 0 Amperes as marked on Dial Shorting Link Closed Fig 10 11 Courtesy of NationalSwitchgear com ...

Страница 12: ... ampere steps and when the scale pointer is set to one of the indicated current values the relay contacts will close in ap proximately 60 minutes if the current increases to 125 percent of the full load value after the full load current has been flowing long enough for the temperature rise to reach a constant value These curves represent the primary performance re quirements of the type BL 1 relay...

Страница 13: ...of current that will ultimately close the relay contacts but variables such as friction and dis crepancies in calibration prevent precise location of the asymptotic value However after making some allowance for such variables a value of 118 of full load current can be considered as the max imum current that will not produce eventual clos ing of the relay contacts when settings are made as describe...

Страница 14: ...supplied in the type BL 1 relay will pick up at 1 0 ampere direct current For detail information on the FT case refer to I L 41 076 SETTINGS CONTACT RATINGS There are two settings to be made on the relay They are as follows Control Capacity Will Break Control Voltage In Amperes Will Close Unit 1 INSTANTANEOUS UNIT Set the element for a pick up current slightly above the maximum current which the a...

Страница 15: ...lower right posi tion Close switch S1 and pass sufficient dc current through the trip circuit to close the contacts of the ICS This value of current should not be greater than the particular ICS nameplate rating The in dicator target should drop freely Repeat above except to pass 85 of ICS nameplate rating current Contacts should not pick up and target should not drop Open switch S1 when checking ...

Страница 16: ...roximately 16 CONTACTOR SWITCH Adjust the stationary core of the switch for a clearance between the stationary core and the moving core of l 64 when the switch is picked up This can be done by turning the relay up side down or by disconnecting the switch and turning it up side down Then screw up the core screw until the moving core starts rotating Now back off the core screw until the moving core ...

Страница 17: ...minimize factors which would introduce calibra tion errors The test current should be interrupted as soon as the contacts close in order to avoid possible damage to the heaters particularly when testing at high values of overload RENEWAL PARTS Repair work can be done most satisfactorily at the factory However interchangeable parts can be furnished to the customers who are equipped for doing repair...

Страница 18: ... 14 30 _ 5 375 36 53 4 0I6 397 250 _ 6 35 0 f 1 031 f 1 031 4 1 031 t 1 031 H 26 19 26 19 26 19 26 19 1 190 32 SCREW 375 1 344 SPACERS FOR 34 14 THIN PANELS 9 53 R PANEL CASE 1 r A 5 16 18 SCREW FOR THICK PANELS USE 5 16 18 STUDS INTERNAL EXTERNAL TOOTHED WASHERS 190 32 SCREW FOR THICK PANELS USE 190 32 STUDS 594 15 09 1 0 25 4 Li nt 5A 77 3 9 i 1 813 i 2 0 i 46 05 i 50 8 i IOV 2 4 6 8 1 V 516 13 ...

Отзывы: