ABB BL-1 Скачать руководство пользователя страница 13

In certain applications it might be desirable to

have faster operation at high values of overload.

This can be accomplished by a change in the con-
tact setting, but the operating time at light
overloads will be reduced to a still greater extent
and thus the full overload capacity of the motor at
light overloads may be made unavailable. Fig. 7
shows time-overload characteristics for the limits
of the adjustment range when the short-circuiting
link is open and when the contact spacing has been
reduced so that the contacts will close in 15

minutes on an overload of 125 percent after cons-
tant temperature has been reached on full load.
For this combination of load and overload, at the

end of the 15-minute  period the pointer should be

moved clockwise to a position where the contacts

just close. It will be possible to move the pointer

sufficiently beyond the 2.5 ampere point to obtain
a 15-minute setting for this value of full load, so

Fig. 7 shows 2.75 amperes as being one end of the

range for the accelerated operation. The upper end

of the range when the shorting link is not used has
been shown as 3.75 amperes, since the pointer
position for a 15-minute  setting at 125 percent of a
3.75 ampere full load current will be near or
somewhat to the left of the 3.5 ampere scale mark-
ing.

It is not expected that these faster operating

curves will be used for general application. They
are presented to show how the relay characteristics
may be modified to meet special conditions. Since
the pointer position must be determined by test, it
could be located to give a time other than 15
minutes at 125 percent overload. If the time were
between 15 and 60 minutes, an approximate
operating curve could be estimated by interpola-

tion between Fig. 5 and 7.

Fig. 8 is similar to Fig. 7 but shows faster  time-

overload curves for full load currents that require
the use of the shorting link.

It will be observed that the curves of Figs. 5

and 6 are approaching an asymptotic position at

125% of full load, and that the curves of Figs. 7

and 8 are farther from their asymptotic position at

125% of full load, as would be expected because of

the shorter time delay. Prior conditions of load
(between zero and full load) will not affect the
value of current that will ultimately close the relay

contacts, but variables such as friction and dis-
crepancies in calibration prevent precise location
of the asymptotic value. However, after making

some allowance for such variables, a value of 118%

of full load current can be considered as the max-

imum current that will not produce eventual clos-
ing of the relay contacts when settings are made as
described for Figs. 5 and 6. For settings made per
Figs. 7 and 8 this current value will be 110% of full
load.

Figs. 9 and 10 show resetting times for the type

BL-1 relay for the shorting link opened or closed.

The complete resetting time is considered to be the

time measured from the moment the relay current
is interrupted until the contacts return to the posi-
tion they would occupy for the steady state condi-
tion of 100 percent of full load current. This com-
plete time is composed of the time required for the
contacts to part and the time for them to travel
back to 100 percent position, and separate curves

are shown for these two components of the com-
plete time. The time will vary depending upon
whether the overload occurs after the motor has
been carrying 100 percent load or from a cold
start, and curves as shown for the two conditions.

The curves are shown for a relay setting at either
end of the adjustment range, and intermediate
values may be obtained by interpolation.

The ambient temperature compensation

provided in the type BL-1 relay causes its
operating time for a given current to remain ap-
proximately the same regardless of changes in the

ambient temperature at the relay. If the ambient

temperature at the motor location varies, the

motor of course will carry a higher overload safely

when the ambient temperature is low. However, a
replica type relay cannot respond to the ambient
temperature at the motor unless it has no ambient

temperature compensating means and unless it is
mounted either adjacent to the motor or, if at a
distance, in a location where there is assurance
that the ambient temperature will vary in exactly
the same way as at the motor. This condition fre-
quently cannot be met. Also, the relay temperature
at the operating point should be very close to that
of the motor at its maximum safe operating

temperature. The type BL-I relay was designed for
a minimum operating temperature much lower
than the safe operating temperature of a motor,

13

13

Courtesy of NationalSwitchgear.com

Содержание BL-1

Страница 1: ...plications However the drop across a portion of the protected circuit such as the interpole field win ding of a machine sometimes can be utilized as a source of energy for the relay CONSTRUCTION AND OPERATION The single element type BL 1 relay consists of a heater unit an instantaneous overcurrent unit 0 two operation indicators and a contactor switch Figures 1 3 The double element type BL 1 relay...

Страница 2: ...Fig 1 Type BL 1 Single Unit Relay without case Front View 2 ...

Страница 3: ...I L 41 553 1G Fig 2 Type BL 1 Double Unit Relay without case Front View 3 Courtesy of NationalSwitchgear com ...

Страница 4: ... currents of short duration The reactor should be removed from the circuit for dc application This is readily accomplished by removing the heavier lead from the two left hand terminals of each thermal unit enclosure of the internal spring will cause it to res pond more slowly than the external spring and a temporary change in contact position would result from a large and rapid change in ambient t...

Страница 5: ... is a small solenoid type switch A cylindrical plunger with a silver disc mounted on its lower end moves in the core of the solenoid As the plunger travels up ward the disc bridges three stationary contacts The coil is in series with the main contacts of the relay and with the trip coil of the breaker When the relay contacts close the coil becomes energized and closes the switch contacts This shun...

Страница 6: ...TACT REACHES FINAL POSITION FOR INITIAL STEADY LOAD INDICATED BELOW ZERO CURRENT INTERNAL TEMP AT APPROX AMBIENT TEMP 70 OF 3 5 AMPS 100 OF 3 5 AMPS V 1 5 1 1 1 1 l i I I I I 1 1 HT V 1 1 1 I I V i T u I I i I l I I I 1 r I I 1 1 X m 9 v 8 V XT T 7 m 6 V p a 5 i m A 1 m X 4 X p jz H t PI A 3 T X7 i V x x 2 I m r r f i 1 i s u s I 1 1 1 1 L 1 i I I I I I I i K J 1 i I i I I I U 1 I I i I k I i I 1 ...

Страница 7: ...OAD APPLIED AFTER MOVING CONTACT REACHES FINAL POSITION FOR INITIAL STEADY LOAD INDICATED BELOW ZERO CURRENT INTERNAL TEMP AT APPROX AMBIENT TEMP 70 OF 5 AMPS 100 OF 5 AMPS l T T i i i V I M V I 1 v J jOk X 9 8 PI 7 J 6 I z4 v 5 7 5 fK 5 V 4 I X 3 Tx X X I iz i ri w i ES i 2 v r 7 i_L l v L C 1 n f LLU i A 1 1 1 1 I 093 MIN AT 1000 L s i i 1 100 200 300 400 500 600 700 800 900 1000 PERCENT OF POIN...

Страница 8: ... I I i I 1 X T j yY T V 4 9 rr 8 is 3 FOR 2 75 AMP SETTING FOR 3 75 AMP SETTING WHEN STARTING FROM 100J OF FULL LOAD CURRENT 6 51 5 5 Y rt Y 5 Y 5r V L 5 1 X Y T j 3 r i K IT 2 1 I i l J i 075 MIN AT 1000J 1 r 100 200 300 400 500 600 700 800 900 1000 PERCENT OF FULL LOAD CURRENT 396063 Curve Fig 7 Current T ime Curves for Special Applications of the Type BL 1 Relay covering Range of F ull Load Cur...

Страница 9: ...pe BL 1 Relay Covering Range of Fufl Load Currents from 4 0 to 5 0 Amperes Contact Settings Determined by Test for 15 Minute Delay with 125 Load Occurring after Moving Contact reaches Final Position for Steady Full Load Shorting Link Closed 9 Courtesy of NationalSwitchgear com ...

Страница 10: ...Fig 9 Contact Opening and Reset Time Curves for the Type BL 1 Reioy for Fult Load Settings of 2 5 to 3 5 Amperes os marked on Dial Shorting Link Open 10 Courtesy of NationalSwitchgear com ...

Страница 11: ...L 41 553 1G Contact Opening and Reset Time Curves for the Type BL 1 Relay for Full Load Settings of 3 75 to 5 0 Amperes as marked on Dial Shorting Link Closed Fig 10 11 Courtesy of NationalSwitchgear com ...

Страница 12: ... ampere steps and when the scale pointer is set to one of the indicated current values the relay contacts will close in ap proximately 60 minutes if the current increases to 125 percent of the full load value after the full load current has been flowing long enough for the temperature rise to reach a constant value These curves represent the primary performance re quirements of the type BL 1 relay...

Страница 13: ...of current that will ultimately close the relay contacts but variables such as friction and dis crepancies in calibration prevent precise location of the asymptotic value However after making some allowance for such variables a value of 118 of full load current can be considered as the max imum current that will not produce eventual clos ing of the relay contacts when settings are made as describe...

Страница 14: ...supplied in the type BL 1 relay will pick up at 1 0 ampere direct current For detail information on the FT case refer to I L 41 076 SETTINGS CONTACT RATINGS There are two settings to be made on the relay They are as follows Control Capacity Will Break Control Voltage In Amperes Will Close Unit 1 INSTANTANEOUS UNIT Set the element for a pick up current slightly above the maximum current which the a...

Страница 15: ...lower right posi tion Close switch S1 and pass sufficient dc current through the trip circuit to close the contacts of the ICS This value of current should not be greater than the particular ICS nameplate rating The in dicator target should drop freely Repeat above except to pass 85 of ICS nameplate rating current Contacts should not pick up and target should not drop Open switch S1 when checking ...

Страница 16: ...roximately 16 CONTACTOR SWITCH Adjust the stationary core of the switch for a clearance between the stationary core and the moving core of l 64 when the switch is picked up This can be done by turning the relay up side down or by disconnecting the switch and turning it up side down Then screw up the core screw until the moving core starts rotating Now back off the core screw until the moving core ...

Страница 17: ...minimize factors which would introduce calibra tion errors The test current should be interrupted as soon as the contacts close in order to avoid possible damage to the heaters particularly when testing at high values of overload RENEWAL PARTS Repair work can be done most satisfactorily at the factory However interchangeable parts can be furnished to the customers who are equipped for doing repair...

Страница 18: ... 14 30 _ 5 375 36 53 4 0I6 397 250 _ 6 35 0 f 1 031 f 1 031 4 1 031 t 1 031 H 26 19 26 19 26 19 26 19 1 190 32 SCREW 375 1 344 SPACERS FOR 34 14 THIN PANELS 9 53 R PANEL CASE 1 r A 5 16 18 SCREW FOR THICK PANELS USE 5 16 18 STUDS INTERNAL EXTERNAL TOOTHED WASHERS 190 32 SCREW FOR THICK PANELS USE 190 32 STUDS 594 15 09 1 0 25 4 Li nt 5A 77 3 9 i 1 813 i 2 0 i 46 05 i 50 8 i IOV 2 4 6 8 1 V 516 13 ...

Отзывы: