INSTALLATION
TUBING CONNECTIONS
3 - 8
4.
Lock all linkage components in place.
TUBING CONNECTIONS
Type AV positioners are available with (Type AV___1___ and
AV___2___) or without (AV___0___) manifolds. The following out-
lines supply air information and describes the piping connections.
Air Supply Pressure
The air supply pressure range is 172 to1034 kilopascals (25 to
150 pounds per square inch gage).
NOTE:
The minimum supply pressure should be 34.4 kilopas-
cals (5 pounds per square inch gage) above the operating pres-
sure required by the actuator.
Air Supply Filtering
An external filter is recommended for Type AV positioners for pri-
mary filtration of the supply air. ABB provides supply air filters as
accessories. Refer to Table
for part numbers.
NOTE:
Primary air supply filters are recommended for position-
ers
with
a manifold (AV___1/2___),
without
a manifold
(AV___0___) or with a gage block (AV___3___).
Figure 3-8. Cam Roller Alignment
T00771A
CAM FOLLOWER ARM
CAM ROLLER
CAM
CAUTION
Do not exceed the maximum supply pressure of 1034 kilo-
pascals (150 pounds per square inch gage). Exceeding this
pressure could cause equipment damage.
Содержание AV1
Страница 1: ...Characterizable Pneumatic Positioners Operating Instructions Actuators Positioners Models AV1 AV2 ...
Страница 24: ......
Страница 42: ......
Страница 51: ...CALIBRATION TROUBLESHOOTING CALIBRATION ADJUSTMENTS 4 9 Figure 4 7 I P Adjustment T00779A ...
Страница 52: ......
Страница 60: ......
Страница 70: ...REPAIR AND REPLACEMENT PILOT VALVE STROKE ADJUSTMENT 8 10 ...
Страница 88: ......
Страница 108: ......
Страница 116: ......
Страница 124: ...Index 4 Index continued Zero suppression 4 4 Zero suppression 4 4 Graph 4 4 ...
Страница 125: ......