QUICK START
TYPE AV1 POSITIONER WIRING
B - 10
4.
Grounding positioners should be done in accordance with local
electrical codes (in U.S, National Electrical Code, ANSI/NFPA 70. In
Canada, Canadian Electrical Code, CSA c22.1). A grounding screw is
provided inside the AV enclosure for grounding, denoted by .
NOTES:
1.
The grounding screw located inside the AV enclosure is a
safety ground and should not be used to ground the shielded pair.
2.
The positioner must be grounded to avoid ground loop
conditions.
TYPE AV1 POSITIONER WIRING
This section applies to the following positioners:
•
Type AV1___1__.
•
Type AV1___2__.
NOTES:
1.
For a Type AV1___0__ positioner, no electrical wiring is
required.
2.
If using a twisted shielded pair for signal wiring, ground one end
of the shielded pair at the source. Trim the other end of the pair,
located inside the enclosure, so that bare wires are not exposed.
1.
If equipped with optional 4 to 20-mA position transmitter (Type
AV1___2__), connect a 24-VDC power supply in series with the
required output load (Table
) to terminals TB1-1 (+) and TB1-2 (-)
(Fig.
). Refer to
for detailed information about posi-
tion transmitters.
2.
If equipped with optional potentiometric position transmitter (Type
AV1___2__), connect a power supply (maximum 35 VDC or 30 VAC)
across TB1-1 and TB1-3. Use the signal across TB1-1 and TB1-2 or
TB1-2 and TB1-3 for position transmitter feedback. Refer to
for detailed information about position transmitters.
NOTE:
Route the wiring inside the positioner so it does not become
entangled with moving parts. A cable clamp (Fig.
inside the positioner so entanglement can be avoided.
3.
Grounding positioners should be done in accordance with local
electrical codes (in U.S, National Electrical Code, ANSI/NFPA 70. In
Canada, Canadian Electrical Code, CSA c22.1). A grounding screw is
provided inside the AV enclosure for grounding, denoted by .
NOTES:
1.
The grounding screw located inside the AV enclosure is a
safety ground and should not be used to ground the shielded pair.
2.
The positioner must be grounded to avoid ground loop
conditions.
Содержание AV1
Страница 1: ...Characterizable Pneumatic Positioners Operating Instructions Actuators Positioners Models AV1 AV2 ...
Страница 24: ......
Страница 42: ......
Страница 51: ...CALIBRATION TROUBLESHOOTING CALIBRATION ADJUSTMENTS 4 9 Figure 4 7 I P Adjustment T00779A ...
Страница 52: ......
Страница 60: ......
Страница 70: ...REPAIR AND REPLACEMENT PILOT VALVE STROKE ADJUSTMENT 8 10 ...
Страница 88: ......
Страница 108: ......
Страница 116: ......
Страница 124: ...Index 4 Index continued Zero suppression 4 4 Zero suppression 4 4 Graph 4 4 ...
Страница 125: ......