AquaMaster™
3 Electrical Installation
IM/AM
Issue 13
27
3.3.4 MIL Connector Input/Output (Option) AquaMag™ x10 Pulse Output Compatibility
Where an existing installation has been wired to operate from the x10 outputs of an AquaMag™, the wiring
of the AquaMaster™ connector can be altered to suit – see Fig. 3.19.
3.3.5 ScanReader Interface (Option)
Fig. 3.19 MIL Connector Input/Output Connections
Note.
Some data logger leads contain components which convert forward and reverse pulses into a
single pulse line with a direction signal. Such leads will NOT work with AquaMaster and are unnecessary
as AquaMaster directly provides the correct signals for these loggers.
Fig. 3.20 ScanReader Connections
Terminal
AquaMag/
AquaMag x10
AquaMag x1
COM
Grey/Blue
Grey/Blue
O/P 1
Orange
White/Red
O/P 2
Blue
White/Black
COM
O/P1
O/P2
O/P3
2-Wire Pad Connection
1.5 m to 40 m
Recommended Cable
ABB STT4009
(or equivalent)
Data
0V
3-Wire Transponder Connection
Data
0V
Transponder
+V
3-terminal PCB
WADX2026
Reading Pad
Cable Colors
Green
+V
Red
Data
Black
0V