35
EntelliGuard R Circuit Breaker Retrofill AKD-6 Installation Manual DEH-41548 07/15
Figure 23. Latching Inner Rail with Outer Rail
Figure 24. Inserting Rod
15.
Remove the racking tool from the storage location on the retrofill front panel and grab the handle and
extend the torque bar from inside the handle.
16.
Use a blade-type screwdriver in the slot or rack-out lock of the breaker (fig. 25) and turn it clockwise 45°to
the right so that the racking handle shutter.
Figure 25. Racking in AKD6—Retrofill
17.
While turning the screwdriver to the right with the racking tool shutter open, insert the racking tool in the
handle-insertion hole, so that it engages the racking mechanism inside the hole.
18.
Line up the racking tool or crank with the handle straight up so that you can get some good leverage or
torque. Then, crank clockwise so that the retrofill starts to move in, slowly sliding forward into the
compartment. Push the breaker in slightly to engage racking cams, if torque seems high at the start.
19.
Rotating clockwise ~37 turns racks the circuit breaker all the way into the enclosure.
20.
As the breaker approaches the TEST position, check the alignment of the fixed and moving parts of the
secondary disconnect contacts (fig. 26). If a motor spring-charge or under-voltage-release is installed, these
devices might activate when approaching the TEST position.