background image

1
0

ON

OFF_N

1
0

1

0

1

X5

2
3

1

X5

2

3

A1

A1

A2

A2

ON

OFF_N
COM

ON

OFF_N
COM

95

96

96

OV

95

+24 V

+24 V

0V

S1
A
B

OFF_N

X5
1

3

2

ON

COM

PLC
PLC

X5

1

2

3

S1

A

B

ON OFF_N COM

PLC PLC       

The functions are descibed with following diagram. "1" means 24 V DC between the control signal and COM. “0” means no voltage between the control signal and

COM.The funktion is made so that ON and OFF_N can be connected in parallel for a common ON/OFF signal. In addition to these signals the funktion limits for the

supply voltage are still valid (closing at 85% and opening at 55%), which is indecated in the diagram by high and low voltage   

According to UL 508

Use wire Cu 75 °C only.

AF(S) 400, 460: Enclosure with min. 36 by 30 by 12 inches shuld be used.

AF(S) 580, 750: Enclosure with min. 48 by 36 by 16 inches should be used and secured by at least three latches.

AF1250: Enclosure with min. 2000 x 1000 x 600 mm should be used.

After a short circuit, ensure that the quarter turn screws are in the correct position.

General

AF-Contactors are fitted with an electronic coil interface. For a given coil, this interface allows the contactor to accept a very wide voltage range. The contactor can 

also be controlled by separate logic control signals from for instance a PLC. Selection of control method is done with switch S1. Control by switching voltage on A1 

and A2 requires the switch in position B while control with logic signals requires the switch in position A. Use of logic control signals also requires a steady supply voltage

on A1 and A2 within the rated voltage range.  

Control by switching voltage on A1 and A2 (switch S1 in position B default factory setting)

Operation of AF-contactors can be done as with conventional contactors by applying and removing voltage on A1 and A2. 

Control with logic control signals (switch S1 in position A)

Use of the logic control signals also requires a steady voltage on terminals A1 and A2 within the operational limits. Minimum pulse lenght for opening and closing: 7 ms.

The function of the logic control signals will no longer be guaranteed when the logic on A1 and A2 is removed. The logic control signals operates with 24 V DC and

consist of two control signals (ON and OFF_N) and a common reference (COM). To close the contactor it is enough with a control pulse at ON and to open it a removal

of voltage from OFF_N.

When used with switches the wiring can be done

according to diagram above.

When used with transistor outputs the wiring can be done

according to diagram above.

Position

Contactor 

closed

Contactor 

open

Control 

voltage

Low

High

Normal range

Operationalrange

85% of lower voltage range level

55% of lower voltage range level

Contactor

Start

Stop

Supply voltage

Relay

Note: Emergency stop should disconnect A1 and A2

Note: Emergency stop should disconnect A1 and A2

Relay

Stop

Start

Supply voltage

Contactor

24V DC Signals:

Status “1” : U=15...33V DC

                  I =10mA at 24V

Status “0” : U=0...5V DC

Supply voltage 

on A1 and A2

Position

Closed

Open

EN

Suitable for use on a circuit capable of delivering not more than the max. symmetrical amperes at the max. voltage shown on the tables below.

 Circuit

Breaker

    A

Short Circiut

    Current

       kA

 Voltage

Maximum

     V

Fuse/Class
       A

AF(S)400

600 

 

  84 

  480

                   700/L 

  84 

  480

600 

 

  42 

  600

                   600/J 

  82 

  600

                   1000/L 

  30 

  600

 Circuit

Breaker

    A

Short Circiut

   Current

       kA

 Voltage

Maximum

     V

Fuse/Class
       A

AF(S)580, AF(S)750

 

                   

800                

  89 

  480

1200 

 

  42 

  480

                   1200/L 

  82 

  480

800 

 

  42 

  600

                   1200/L 

  82 

  600

UL Short Circuit Data

AF(S)400

AF(S)460

Additional Ratings

 Circuit

Breaker

    A

Short Circiut

    Current

       kA

 Voltage

Maximum

     V

Fuse/Class
       A

AF(S)460

800 

 

  84 

  480

                   800/L 

  84 

  480

800 

 

  42 

  600

                   600/J 

  82 

  600

                   1000/L 

  30 

  600

Capacitor Switching

208V, 119 kvar, 330 FLA

240V, 137 kvar, 330 FLA

480V, 274 kvar, 330 FLA

600V, 343 kvar, 330 FLA

208V, 142 kvar, 396 FLA

240V, 164 kvar, 396 FLA

480V, 329 kvar, 396 FLA

600V, 410 kvar, 396 FLA

AF(S)580

208V, 178 kvar, 495 FLA

240V, 205 kvar, 495 FLA

480V, 411 kvar, 495 FLA

600V, 514 kvar, 495 FLA

 AF(S)750

208V, 214 kvar, 595 FLA

240V, 247 kvar, 595 FLA

480V, 494 kvar, 595 FLA

600V, 618 kvar, 595 FLA

Notice.

 

  This product has been designed for environment A. Use of this product in environment B may cause unwanted electromagnetic disturbances 

 

  in which case the user may be required to take adequate mitigation measures.

B

COM

PLC
PLC

OFF_N

ON

S1
A

3

X5
1

2

ON

(0.14 in)

2.6 lb.in

0.3  Nm

ø 3.5 mm

Wire dimensions for PLC interface.

Wire strip length

5-6 mm

(0.2-0.24 in)

3 x AWG 22 ... 14

3 x 0.2...2 mm²

1SFC380023

 

5/13

 

Содержание AF1250

Страница 1: ...ith electrotechnical expertise only es Advertencia Tensión peligrosa Consulte las instrucciones de funcionamiento Antes de trabajar con este dispositivo desconecte y bloquee la corriente Atención La instalación debe ser realizada únicamente por un técnico electricista et Hoiatus Elektrilöögi oht Lisateavet vaadake kasutusjuhendist Enne selle seadmega töötamist ühendage lahti ja lukustage toide Täh...

Страница 2: ...рическое напряжение Обратитесь к инструкциям по эксплуатации Отключите питание и обесточьте устройство перед началом работ Внимание Установка должна выполняться только специалистом по электротехническим работам sk Výstraha Nebezpečné napätie Pozrite si návod na použitie Pred začatím prác na tomto zariadení odpojte a zablokujte napájanie Pozor Inštaláciu smie vykonávať len osoba s odbornými znalosť...

Страница 3: ...S 400 AF S 160 Max 45mm Max 47mm M12 1 Nm 9 lb in 1 4 x4 torx 20 2x3 ZW 460 750 1250 1 4 x4 ZL 400 1250 2x3 AF S 400 AF S 460 AF S 580 AF S 750 x3 ZL 400 460 580 750 1250 2x3 1 4 x4 AF 1250 AF S 400 750 22 Nm 195 lb in AF 1250 35 Nm 310 lb in Notice Main Contact sets change fixed and moving contacts at the same time For AF580 and AF750 contacts needs to be replaced after 750k operations 1SFC380023...

Страница 4: ...M5 M 6 72 249 AF S 400 AF S 460 2 9 Nm 25 7 lb in 3 5 Nm 31 lb in Notice Be aware of the polyester barrier Make sure it s still in place after step 1 and step 2 Applies for AF580 AF750 and AF1250 Polyester barrier AF S 580 AF S 750 AF1250 1SFC380023 4 13 ...

Страница 5: ...gic control signals operates with 24 V DC and consist of two control signals ON and OFF_N and a common reference COM To close the contactor it is enough with a control pulse at ON and to open it a removal of voltage from OFF_N When used with switches the wiring can be done according to diagram above When used with transistor outputs the wiring can be done according to diagram above Position Contac...

Страница 6: ...z ab Der 24VDC Eingang arbeitet mit den Steuersignalen ON und OFF_N und dem Null Potential COM Das Schütz wird wird durch einen kurzen Impuls 7 ms an der Klemme ON eingeschaltet und durch eine kurze Unterbrechung der Spannung 7ms an der Klemme OFF_N ausgeschaltet l a h c S n e t k a t n o K t i m g n u r e u e t s n A n a l p t l a h c S tplan Ansteuerung mit Transistorausgängen Die Funktion des A...

Страница 7: ... et A2 Temps minimum de l impulsion pour l ouverture et la fermeture 7ms Le fonctionnement n est garanti que si les bornes A1 et A2 sont alimentées Les signaux logiques de commande fonc tionnent sous 24VDC et sont composés de deux signaux de commande ON et OFF_N et d une référence commune COM Pour fermer le con tacteur une impulsion en tension sur l entrée ON et pour le fermer il suffit de retirer...

Страница 8: ...F_N och en gemensam referens COM För tillslag av kontaktorn räcker det med en puls på ON och för frånslag kopplas spänningen bort på OFF_N När omkopplare används kan inkopplingen göras enligt detta schema När transistorutgångar används kan inkopplingen göras enligt detta schema Funktionerna beskrivs i nedanstående diagram 1 betyder 24V DC mellan manöversignalen och COM 0 betyder ingen spänning mel...

Страница 9: ...rno del range di tensione della bobina stessa sui terminali A1 e A2 Minima lunghezza dell impulso per aprire e chiudere 7ms Il funzionamento del segnale di controllo logico non è più garantito se viene a mancare tensione tra A1 e A2 Il segnale logico lavora con 24Vcc e consiste in due segnali ON e OFF_N e di un comune COM Per chiudere il contattore è sufficiente una tensione impulsiva su ON per ap...

Страница 10: ... en los terminales A1 y A2 del rango nominal adecuado La mínima duración del pulso para la apertura o el cierre del contactor es de 7ms El correcto funcionamiento de las señales de control lógicas no se garantiza si no se aplica tensión en A1 y A2 Las señales de control lógicas funcionan a 24Vcc y consiste en dos señales ON y OFF_N y un común COM Para cerrar el contactor es suficiente con un pulso...

Страница 11: ...ja A2 Kelan ohjaus ei toimi ilman kelajännitettä navoilla A1 ja A2 Ohjaussignaalin pituus on oltava vähintään 7ms Logii kan ohjaussignaali toimii 24VDC jännitteellä ja koostuu kahdesta erillisestä ohjaussignaalista ON ja OFF_N sekä yhteinen 0V COM Kontaktori vetää kun jännitepulssi tuodaan liittimeen ON ja kontaktori päästää kun jän nite poistetaan liittimeltä OFF_N s u a j h O ä i m i k t y k ä s...

Страница 12: ...接触器可以象常规接触器一样来控制 在A1和A2端施加或去除 控制电压 通过逻辑信号控制 拨码开关在位置A 使用逻辑控制时 同样需要在A1及A2端子上施加一个稳定的电 压 电压是在线圈额定电压范围内 吸合及打开时所需的最小 脉冲持续时间 7ms 当A1及A2端子上没加控制电压时 逻辑控 制的功能就无法实现 逻辑控制信号的操作是通过直流24V来实 现的 包括两个控制信号 ON及OFF_N 及公共端 COM 在O N端子上加一个电压脉冲可以是接触器吸合 去除OFF_N上的电 压可以使接触器打开 下图给出了此功能的逻辑图 1 表示24 V DC 加在控制信号端及公共端 0 表示控制信号端及公 共端之间无控制电压 对于一个通常的启 停信号 可 以通过并联连接ON及OFF_N来实现 除了以上信号外 对线圈电压的控制仍然有效 85 时吸合 55 时打 开 电压范围可以参见上页附图 当使用触点控制时 可按...

Страница 13: ...дать управляющий импульс на вход ON а для размыкания необходимо снять напряжение со входа OFF_N Работа контактора может быть описана следующей диаграммой 1 означает наличие потенциала 24В DC между входом управления и общим входом COM 0 означает отсутствие потенциала между входом управления и общим входом COM Для работы контактора необходимо подсоединить входы ON и OFF_N к одному общему источнику с...

Отзывы: