Analogue Input AE/S 4.2 is used to record analogue data. Four conventional
sensors can be connected to AE/S 4.2. The connection to the bus is
established using the enclosed bus connection terminal at the front of the
device. The device is ready for operation after connecting the mains voltage
of 115...230 V AC and the bus voltage. Analogue Input AE/S 4.2 is
parameterised using ETS2 V1.3 or higher.
Fig. 1: Analogue Input AE/S4.2
Power supply
– Bus voltage
21 … 32 V DC
– Power input, bus
< 10 mA
– Mains voltage U
s
115 ... 230 V AC (+ 10% – 15%), 50 / 60 Hz
– Power consumption
Max. 11 W, at 230 V AC
– Power input, mains
80/40 mA, at 115/230 V AC
– Leakage loss
Max. 3 W, at 230 V AC
Auxiliary voltage output
to supply the sensors
– Nominal voltage U
n
24 V DC
– Nominal current I
n
300 mA
Inputs
– Number
4 independent sensor inputs
– Input signal/resolution/accuracy
0 – 1 V / 1 mV / +/– 2% of the upper limit
of the effective range (of ULE)
0 – 5 V / 5 mV / +/– 2% of ULE
0 – 10 V / 10 mV / +/– 2% of ULE
1 – 10 V / 10 mV / +/– 2% of ULE
0 – 20 mA / 20 μA / +/– 2% of ULE
4 – 20 mA / 20 μA / +/– 2% of ULE
0 – 1000 ohm resistance / 2.5 ohm /
+/– 2% of ULE
PT100 2-conductor technology
– 30...+ 70 °C / 0.1 K / +/– 1 K of ULE
PT100 2-conductor technology
– 200...+ 800 °C / 1.5 K / +/– 10 K of ULE
Floating contact interrogation
(pulse width min. 100 ms)
–
Input resistance to voltage measurement >
50
kohm
–
Input resistance to current measurement 260 ohm
Connections
– EIB / KNX
Via bus connection terminal, screwless
– Mains voltage
Via screw terminals
– Supply for the sensors
Via screw terminals
– Sensor inputs
Via screw terminals
Connecting terminals
– Screw terminals
0,2 ... 2,5 mm
2
finely stranded
0,2 ... 4,0 mm
2
single-core
– Tightening torque
Max. 0.6 Nm
Operating and display elements
– Programming LED
For assigning the physical address
– Programming button
For assigning the physical address
Table 1: Technical data part 1
2CDC 071 263 F0005