19
ABB i-bus
®
EIB / KNX
Commissioning
Modify limits via the bus
Options: no/yes
This parameter is used to define whether it is possible to
Modify limits via
the bus
. If
yes
is selected, the “Modify – Channel A threshold 1 lower limit”
and “Modify – Channel A threshold 1 upper limit” communication objects
also appear.
Note:
The value formats for these communication objects are
identical to the format set under the
Send output valu
e as
parameter in the
Channel A
parameter window.
The values must be sent in the same format as the output
value for the channel.
Data type of threshold value object
Options:
1 bit/1 byte [0...255]
If the
1 bit
option is set for the
Data type of threshold value object
parameter,
the following parameters appear.
Send if threshold value falls below
Options:
Do not send a telegram
Send an ON telegram
Send an OFF telegram
Send if threshold value exceeds
Options:
Do not send a telegram
Send an ON telegram
Send an OFF telegram
Option
Do not send a telegram
= No reaction occurs
Option
Send an ON telegram
= Send telegram value “1”
Option
Send an OFF telegram
= Send telegram value “0”
Minimum duration of the underflow
Minimum duration of the overrange
Options:
none/5 s/10 s/30 s/1 min/5 min/10 min/30 min/1 h/6 h/
12 h/24 h
Option
none
= Send threshold value directly
The further time options can be used to select a minimum duration.
If the send condition reverts within the minimum duration, nothing is sent.