16
ABB i-bus
®
EIB / KNX
Commissioning
3.2.2.2 Parameter window
“A – Output”
Fig. 12: Parameter window “Channel A – Output”
Scanning frequency
The sensor signal of channel A is measured once per second.
Filter
Options:
inactive
low (mean value over 4 measurements)
average (mean value over 16 measurements)
high (mean value over 64 measurements)
This parameter is used to set a filter. The output value can thus be set
as a mean value using three different options.
Option:
inactive
= Filter is not active
Option:
low
= Output value as
mean value over 4 measurements
Option:
average
= Output value as
mean value over 16 measurements
Option: high = Output value as
mean value over 64 measurements
Note:
In the case of the
average
setting, for example, it takes
16 seconds until the output value is reached after an
immediate change in the sensor signal.