![ABB AE/S 4.2 Скачать руководство пользователя страница 30](http://html.mh-extra.com/html/abb/ae-s-4-2/ae-s-4-2_product-manual_3601030.webp)
28
ABB i-bus
®
EIB / KNX
Commissioning
Sensor output
Options:
0 – 1 V/0 – 5 V/0 – 10 V/1 – 10 V
0 – 20 mA/4 – 20 mA/0 – 1000 ohm/
Floating contact interrogation /
PT100 2-conductor technology – 30...+ 70 °C/
PT100 2-conductor technology – 200...+ 800 °C
This parameter is used to set the
Sensor output
. The data can be found
in the technical documentation of the sensor manufacturer.
Send output value as
This parameter is fixed as 2 byte [EIB floating point].
Temperature offset in 0.1 K [– 50...+ 50]
Options:
– 50...0...+ 50
An additional maximum offset of + /– 5 K (Kelvin) can be added to
the recorded temperature using this parameter.
Line fault compensation
Options:
non/via cable length/via cable resistance
This parameter is used to set a
Line fault compensation
to compensate
for the measuring error caused by the cable resistance.
In the case of the
via cable length
and
via cable resistance
options, further
parameters appear – see next page.