538 Fault tracing
000B (Asynchronous motors only)
Speed dropped to zero during
ID run.
Contact your local ABB representative.
000C (Permanent magnet motors
only) First acceleration did not
finish within reasonable time.
Contact your local ABB representative.
000D (Permanent magnet motors
only) Second acceleration did
not finish within reasonable
time.
Contact your local ABB representative.
000E…0010 Internal error.
Contact your local ABB representative.
FF7E
Follower
A follower drive has tripped.
Check the auxiliary code. Add 2 to the
code to find out the node address of the
faulted drive.
Correct the fault in the follower drive.
FF81
FB A force trip
A fault trip command has been
received through fieldbus
adapter A.
Check the fault information provided by
the PLC.
FF82
FB B force trip
A fault trip command has been
received through fieldbus
adapter B.
Check the fault information provided by
the PLC.
FF8E
EFB force trip
A fault trip command has been
received through the
embedded fieldbus interface.
Check the fault information provided by
the Modbus controller.
Code
(hex)
Fault
Cause
What to do
Содержание ACS880-x04
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 primary control program Firmware manual ...
Страница 4: ......
Страница 18: ...18 Using the control panel ...
Страница 24: ...24 Control locations and operating modes ...
Страница 111: ...Application macros 111 Fieldbus control macro This application macro is not supported by the current firmware version ...
Страница 112: ...112 Application macros ...
Страница 496: ...496 Additional parameter data ...
Страница 544: ...544 Fault tracing ...
Страница 602: ...602 Control chain diagrams ...