Start-up and acceptance test 45
4
Start-up and acceptance test
Contents of this chapter
This chapter describes the start-up and acceptance procedure of the safety function.
Safety encoder interface
When you use a safety pulse encoder in the safety application, validate the safety encoder
interface as described in
FSO-21 safety functions module user’s manual
(3AXD50000015614 [English]), chapter
Verification and validation
.
Start-up and acceptance test
You need the Drive composer pro PC tool to perform the start-up and acceptance test.
Initial status: Make sure that the drive is ready for use, that is, you have done the tasks of
the drive start-up procedure. See the hardware manual.
Action
WARNING!
Obey the
, page
. If you ignore them, injury or death, or
damage to the equipment can occur.
Checks and settings with no voltage connected
If you have done any connections of the emergency stop circuit on site (such as wiring of additional
emergency stop buttons, connection of shipping splits of large drives, etc.), check the connections
against the appropriate circuit diagrams.
Drives with R8i inverter modules: Check that the STO OUT output on the inverter control unit [A41] is
chained to the STO inputs of all inverter modules. The STO circuit is disabled in spare part modules.
Содержание ACS880-17
Страница 4: ......
Страница 7: ...7 Document library on the Internet 57...
Страница 8: ...8...
Страница 34: ...34 Option description and instructions...
Страница 48: ...48 Start up and acceptance test...
Страница 56: ...56 Technical data...
Страница 58: ...3AUA0000145921 Rev E EN 2018 02 02 Contact us www abb com drives www abb com drivespartners...