44 Parameter settings
Drive
Parameter 31.22 STO indication run/stop
The parameter setting in ACS880 primary control program:
•
parameter
31.22 STO indication run/stop
is set to value
Warning/Warning
.
We recommend that you do not set parameter
31.22 STO indication run/stop
to value
0
,
1
or
2
.
This prevents the drive from making a fault every time the FSO module activates the
STO function.
Safety pulse encoder parameters
The drive parameter settings in ACS880 primary control program when you use a safety
pulse encoder:
•
parameter
90.41 Motor feedback selection
is set to value
Encoder 1
.
•
parameter
90.45 Motor feedback fault
is set to value
Warning
.
Note
: If you want that the drive trips on encoder faults, set this parameter to value
Fault
. For more information, see the firmware manual.
•
parameter
92.21 Encoder cable fault mode
is set to value
A, B, Z
.
SS1 ramp parameters
You must set these parameters only for the Emergency stop, stop category 1 option.
200.112 SAR1 ramp time to zero
is set to
0
, drive parameters define the
stop ramp that is used in the SS1 function (stop category 1). Set:
•
21.04 Emergency stop mode
to value
Eme ramp stop (Off3)
•
23.23 Emergency stop time
to a suitable value.
Also in this case, the FSO module monitors the actual stop ramp (ramp monitoring or time
monitoring).
For more information, see the firmware manual of your drive.
Содержание ACS880-17
Страница 4: ......
Страница 7: ...7 Document library on the Internet 57...
Страница 8: ...8...
Страница 34: ...34 Option description and instructions...
Страница 48: ...48 Start up and acceptance test...
Страница 56: ...56 Technical data...
Страница 58: ...3AUA0000145921 Rev E EN 2018 02 02 Contact us www abb com drives www abb com drivespartners...