Parameter settings 41
Changing the stop category from 0 to 1
Stop category 0 is the default setting. This category uses the STO function of the FSO
module. Stop category 1 uses the SS1 function of the FSO module.
SS1.15
SS1-r ramp zero
speed delay for STO
0 ms
Sets an extra delay time for the drive STO activation at the zero
speed in the SS1 function.
With this parameter, the FSO module delays the STO activation
so that the drive is able to reach the axle zero speed before the
FSO module activates the STO function.
The delay counter starts when the motor speed reaches the
zero speed limit (parameter
). After
this delay has elapsed, the FSO module activates the drive STO
function. You can use this parameter when the motor rotates a
heavy load (high inertia).
Note
: The FSO module activates the drive STO immediately if
the drive stops modulating before the delay has passed (that is,
the motor actual speed reaches 0 rpm).
Adjust the default value when necessary.
SAR1 ramp settings
200.112
SAR1 ramp time to
zero
2000 ms
Sets the target time for the stop ramp SAR1 that is used in the
SS1 function. Adjust the default value when necessary.
Target time = The time in which the drive decelerates the
motor(s) from speed
to zero.
Note:
With value
0 ms
, the drive uses the emergency stop ramp
set by drive parameter
23.23
(see section
below). Also in this case, the FSO module monitors
the actual ramp (ramp monitoring or time monitoring).
200.202
SAR speed scaling
1500 rpm
Sets a speed value that the FSO module uses as a reference
point in ramp parameter calculations (see SAR1 ramp
parameters
,
and
).
Adjust the default value when necessary.
SARx.02 SAR initial allowed
range
100 ms
Sets the initial allowed range for the SAR0/SAR1 ramp. This
parameter moves the location of the maximum monitoring ramp
forward on the time axis, when monitoring is started. The slope
of the ramp stays the same as defined with parameters
and
. For more information, see the FSO module
user’s manual.
Time monitoring: This value has no effect in the operation.
Ramp monitoring: Adjust the default value when necessary.
SARx.21 SAR1 min ramp time
to zero
1000 ms
Sets the minimum ramp time for the SAR1 ramp monitoring.
Time monitoring: This value has no effect in the operation.
Ramp monitoring: Sets the minimum stop ramp time for the
emergency stop. Adjust the default value when necessary.
Note
: With value
0 ms
, the minimum ramp is not monitored.
SARx.22 SAR1 max ramp time
to zero
3000 ms
Sets the maximum ramp time for the SAR1 ramp monitoring.
Time monitoring: This value has no effect in the operation.
Ramp monitoring: Sets the maximum stop ramp time for the
emergency stop. Adjust the default value when necessary.
SBC usage
SBC.15
SSE/SS1 SBC speed 0 rpm
Sets the absolute speed below which the FSO module activates
the brake (SBC) while ramping.
0 rpm
: This feature is not in use.
In this manual, we assume that you do not use a brake. If you
do, you must take care of its on/off control by the FSO module
and change this and other settings. See the FSO module user’s
manual.
Index
Name
Example
value
Description
Содержание ACS880-17
Страница 4: ......
Страница 7: ...7 Document library on the Internet 57...
Страница 8: ...8...
Страница 34: ...34 Option description and instructions...
Страница 48: ...48 Start up and acceptance test...
Страница 56: ...56 Technical data...
Страница 58: ...3AUA0000145921 Rev E EN 2018 02 02 Contact us www abb com drives www abb com drivespartners...