• Make sure that the drive type designation label includes the applicable marking.
•
DANGER - Risk of electric shock.
After disconnecting the input power, always wait for
5 minutes to let the intermediate circuit capacitors discharge before you start working on
the drive, motor or motor cable.
• The drive is to be used in a heated, indoor controlled environment. The drive must be
installed in clean air according to the enclosure classification. Cooling air must be clean,
free from corrosive materials and electrically conductive dust.
• The maximum surrounding air temperature is 40 °C at rated output current. The output
current is derated for 40 … 55 °C.
• The drive is suitable for use in a circuit capable of delivering not more than 100 kA rms
symmetrical amperes, 600 V maximum when protected by the UL fuses given elsewhere
in this chapter.
• The cables located within the motor circuit must be rated for at least 75 °C in UL-compliant
installations.
• The input cable must be protected with fuses or circuit breakers. These protective devices
provide branch circuit protection in accordance with the national regulations (National
Electrical Code (NEC) or Canadian Electrical Code). Obey also any other applicable
local or provincial codes.
WARNING!
The opening of the branch-circuit protective device may be an indication that
a fault current has been interrupted. To reduce the risk of fire or electric shock,
current-carrying parts and other components of the device should be examined
and replaced if damaged.
• The drive provides motor overload protection. This feature is not enabled when the drives
leaves the ABB factory. For enabling this motor overload protection, see the firmware
manual.
• The drive overvoltage category according to IEC 60664-1 is III
EU Declaration of Conformity (Machinery Directive)
See
The Safe torque off function (page 215)
Disclaimers
■
Generic disclaimer
The manufacturer shall have no obligation with respect to any product which (i) has been
improperly repaired or altered; (ii) has been subjected to misuse, negligence or accident;
(iii) has been used in a manner contrary to the manufacturer’s instructions; or (iv) has failed
as a result of ordinary wear and tear.
Technical data 201
Содержание ACS880-14
Страница 1: ...ABB INDUSTRIAL DRIVES ACS880 14 drive modules 132 400 kW 200 400 hp Hardware manual...
Страница 2: ......
Страница 4: ......
Страница 14: ...14...
Страница 24: ...24...
Страница 30: ...30...
Страница 54: ...54...
Страница 64: ...64...
Страница 98: ...98...
Страница 114: ...With twin connectors in the control panel holder 1 2 3 1 114 Electrical installation...
Страница 115: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 115 11...
Страница 142: ...4 5 6 3 3 1 1 1 1 2 142 Installation example with full cabling panels option H381...
Страница 150: ...150 Installation example with full cabling panels option H381...
Страница 156: ...156...
Страница 204: ...Standard configuration 204 Dimension drawings...
Страница 205: ...Location of power cable connection terminals with options H370 H356 3AXD50000038012 Dimension drawings 205...
Страница 206: ...Drive module with options 0B051 H356 0H371 206 Dimension drawings...
Страница 207: ...Configuration with option H381 3AXD50000323210 Dimension drawings 207...
Страница 208: ...LCL filter module 208 Dimension drawings...
Страница 212: ...External control unit 3AXD50000011687 212 Dimension drawings...
Страница 230: ...Declaration of conformity 230 The Safe torque off function...
Страница 236: ...Combi screw M8 30 Hex 20 N m 14 75 lbf ft Tapping screw M6 12 Torx T30 Hex 8 N m 71 lbf in 8 10 9 11 12 236...
Страница 241: ...241...
Страница 246: ...246...