Use as motor cabling
Use as input power cabling
Cable type
Yes
Yes
PE
Symmetrical shielded (or armored)
cable with three phase conductors
and symmetrically constructed PE
conductor and a shield (or armor)
Yes
Yes
PE
Symmetrical shielded (or armored)
cable with three phase conductors
and a shield (or armor), and separ-
ate PE conductor/cable
1)
1) A separate PE conductor is required if the conductivity of the shield (or armor) is not sufficient for the PE use.
Alternate power cable types
Use as motor cabling
Use as input power cabling
Cable type
Yes with phase conductor smaller
than 10 mm
2
(8 AWG) Cu, or motors
up to 30 kW (40 hp).
Yes with phase conductor smaller
than 10 mm
2
(8 AWG) Cu.
PVC
Note:
Shielded or armored cable, or
cabling in metal conduit is always
recommended to minimize radio fre-
quency interference.
Four-conductor cabling in PVC con-
duit or jacket (three phase conduct-
ors and PE)
Yes with phase conductor smaller
than 10 mm
2
(8 AWG) Cu, or motors
up to 30 kW (40 hp)
Yes
EMT
Four-conductor cabling in metal
conduit (three phase conductors and
PE), eg, EMT, or four-conductor ar-
mored cable
Yes with motors up to 100 kW
(135 hp). A potential equalization
between the frames of motor and
driven equipment is required.
Yes
Shielded (Al/Cu shield or armor)
1)
four-conductor cable (three phase
conductors and a PE)
84 Guidelines for planning the electrical installation
Содержание ACS880-14
Страница 1: ...ABB INDUSTRIAL DRIVES ACS880 14 drive modules 132 400 kW 200 400 hp Hardware manual...
Страница 2: ......
Страница 4: ......
Страница 14: ...14...
Страница 24: ...24...
Страница 30: ...30...
Страница 54: ...54...
Страница 64: ...64...
Страница 98: ...98...
Страница 114: ...With twin connectors in the control panel holder 1 2 3 1 114 Electrical installation...
Страница 115: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 115 11...
Страница 142: ...4 5 6 3 3 1 1 1 1 2 142 Installation example with full cabling panels option H381...
Страница 150: ...150 Installation example with full cabling panels option H381...
Страница 156: ...156...
Страница 204: ...Standard configuration 204 Dimension drawings...
Страница 205: ...Location of power cable connection terminals with options H370 H356 3AXD50000038012 Dimension drawings 205...
Страница 206: ...Drive module with options 0B051 H356 0H371 206 Dimension drawings...
Страница 207: ...Configuration with option H381 3AXD50000323210 Dimension drawings 207...
Страница 208: ...LCL filter module 208 Dimension drawings...
Страница 212: ...External control unit 3AXD50000011687 212 Dimension drawings...
Страница 230: ...Declaration of conformity 230 The Safe torque off function...
Страница 236: ...Combi screw M8 30 Hex 20 N m 14 75 lbf ft Tapping screw M6 12 Torx T30 Hex 8 N m 71 lbf in 8 10 9 11 12 236...
Страница 241: ...241...
Страница 246: ...246...