Operation principle
1. The Safe torque off activates (the activation switch is opened, or safety relay contacts
open).
2. The STO inputs of the drive control unit de-energize.
3. The control unit cuts off the control voltage from the output IGBTs.
4. The control program generates an indication as defined by parameter
31.22
(see the
firmware manual of the drive).
The parameter selects which indications are given when one or both STO signals are
switched off or lost. The indications also depend on whether the drive is running or
stopped when this occurs.
Note:
This parameter does not affect the operation of the STO function itself. The STO
function will operate regardless of the setting of this parameter: a running drive will stop
upon removal of one or both STO signals, and will not start until both STO signals are
restored and all faults reset.
Note:
The loss of only one STO signal always generates a fault as it is interpreted as a
malfunction of STO hardware or wiring.
5. The motor coasts to a stop (if running). The drive cannot restart while the activation
switch or safety relay contacts are open. After the contacts close, a reset may be needed
(depending on the setting of parameter
31.22
). A new start command is required to start
the drive.
222 The Safe torque off function
Содержание ACS880-14
Страница 1: ...ABB INDUSTRIAL DRIVES ACS880 14 drive modules 132 400 kW 200 400 hp Hardware manual...
Страница 2: ......
Страница 4: ......
Страница 14: ...14...
Страница 24: ...24...
Страница 30: ...30...
Страница 54: ...54...
Страница 64: ...64...
Страница 98: ...98...
Страница 114: ...With twin connectors in the control panel holder 1 2 3 1 114 Electrical installation...
Страница 115: ...With FDPI 02 modules OPEN TERMIN ATED 1 1 2 2 OPEN TERMINATED 3 Electrical installation 115 11...
Страница 142: ...4 5 6 3 3 1 1 1 1 2 142 Installation example with full cabling panels option H381...
Страница 150: ...150 Installation example with full cabling panels option H381...
Страница 156: ...156...
Страница 204: ...Standard configuration 204 Dimension drawings...
Страница 205: ...Location of power cable connection terminals with options H370 H356 3AXD50000038012 Dimension drawings 205...
Страница 206: ...Drive module with options 0B051 H356 0H371 206 Dimension drawings...
Страница 207: ...Configuration with option H381 3AXD50000323210 Dimension drawings 207...
Страница 208: ...LCL filter module 208 Dimension drawings...
Страница 212: ...External control unit 3AXD50000011687 212 Dimension drawings...
Страница 230: ...Declaration of conformity 230 The Safe torque off function...
Страница 236: ...Combi screw M8 30 Hex 20 N m 14 75 lbf ft Tapping screw M6 12 Torx T30 Hex 8 N m 71 lbf in 8 10 9 11 12 236...
Страница 241: ...241...
Страница 246: ...246...