Default I/O connections 

XPOW 

External power input 

1

+24VI

24 V DC, 2

 

A

2

GND

XAI 

Reference voltage and analog inputs

1

+VREF

10 V DC, 

R

L

 1…10 kohm

2

-VREF

-10 V DC, 

R

L

 1…10 kohm

3

AGND

Ground

4

AI1+

Speed reference

 0(2)…10 V, 

R

in

 > 

200 kohm 

5

AI1-

6

AI2+

By default not in use. 0(4)…20 mA, 

R

in

 = 

100 ohm

7

AI2-

J1

J1

AI1 current/voltage selection jumper

J2

J2

AI2 current/voltage selection jumper

XAO

 Analog 

outputs

1

AO1

Motor speed rpm

 0…20 mA, 

R

L

 <  

500 ohm

2

AGND

3

AO2

Motor current

 0…20 mA, 

R

L

 < 500 ohm

4

AGND

XD2D

Drive-to-drive link

1

B

Drive-to-drive link

2

A

3

BGND

J3

J3

Drive-to-drive link termination switch

XRO1, XRO2, XRO3 

Relay outputs

11

NC

Ready

250 V AC / 30 V DC
2 A

12

COM

13

NO

21

NC

Running

250 V AC / 30 V DC
2 A

22

COM

23

NO

31

NC

Faulted(-1)

250 V AC / 30 V DC
2 A

32

COM

33

NO

XD24

Digital interlock

1

DIIL

Run enable

2

+24VD

+24 V DC 200 mA 

1)

3

DICOM

Digital input ground

4

+24VD

+24 V DC 200 mA 

1)

5

DIOGND Digital input/output ground

J6

Ground selection switch

XDIO

Digital input/outputs

1

DIO1

Output: Ready

2

DIO2

Output: Running

XDI

Digital inputs

1

DI1

Stop (0) / Start (1) 

2

DI2

Forward (0) / Reverse (1) 

3

DI3

Reset

4

DI4

Acceleration & deceleration select

5

DI5

Constant speed 1 (1 = On)

6

DI6

By default not in use.

XSTO  

Safe torque off

1

OUT1

Safe torque off. Both circuits must be 
closed for the drive to start.

2

SGND

3

IN1

4

IN2

X12

Safety functions module connection

X13

Control panel connection

X205

Memory unit connection

Wire sizes: 

0.5 … 2.5 mm

2

 

(24…12 AWG)  

Tightening 

torques: 0.5 N·m 

(5 lbf·in) for both 

stranded and 

solid wiring.

1)

 Total load capacity 

of these outputs is 

4.8 W (200 mA / 

24 V) minus the 

power taken by DIO1 

and DIO2.

Fault

Содержание ACS880-01 Series

Страница 1: ...After unpacking protect the drive from dust debris and moisture Make sure that these items are included cable conduit box frames R5 R9 of IP21 UL Type 1 drive mounting template control panel quick ins...

Страница 2: ...erial The installation surface is as close to vertical as possible and strong enough to support the drive There is sufficient free space around the drive for cooling maintenance and operation For the...

Страница 3: ...the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and midpoint grounded delta systems IT systems ungrounded or high resistance grounded TT syste...

Страница 4: ...e c Shield of a VFD shielded cable Ground the shield 360 under drive s grounding clamp then twist with the ground conductors and connect under the drive s ground terminal Ground the shield also 360 a...

Страница 5: ...to Terminal data For frames R1 R3 Ground the cable shields 360 degrees in the Romex clamp IP21 Type 1 units For IP55 Type 12 ground the cable shield 360 degrees on grounding shelf as shown in R4 R5 a...

Страница 6: ...als as possible to prevent inductive coupling 1 Cut a hole into the rubber grommet and slide the grommet onto the cable 2 Ground the outer shield of the cable 360 degrees under the grounding clamp Kee...

Страница 7: ...22 COM 23 NO 31 NC Faulted 1 250 V AC 30 V DC 2 A 32 COM 33 NO XD24 Digital interlock 1 DIIL Run enable 2 24VD 24 V DC 200 mA 1 3 DICOM Digital input ground 4 24VD 24 V DC 200 mA 1 5 DIOGND Digital in...

Страница 8: ...1 5 N m 1 5 N m R1 R3 R4 R9 Note Use an un used ground clamp screw If none available ground as shown 1 2 3 2 2 Note The illustration shows frame R2 All frame sizes are similar M4 8 Torx T20 2 N m 17 l...

Страница 9: ...torques refer to Terminal data Frames R4 R5 Install the EMC shroud separating the input and output cabling if not installed yet If brake chopper is in use Connect the brake resistor conductors to the...

Страница 10: ...xt Use the arrow keys and to move the cursor or change values depending on the active view Key shows a context sensitive help page 1 Power up the drive Make sure that you have the motor name plate dat...

Страница 11: ...in the master station 58 05 Parity 8 EVEN 1 default Selects the parity and stop bit setting Use the same setting as in the master station 58 06 Communication control Refresh settings Validates any ch...

Страница 12: ...880 01 Frame size Nominal ratings Fuses3 Typical power cable Typical power loss 8 Input current Output current Motor power1 gG fuse4 DIN 43620 aR fuse2 4 DIN 43620 ULclass T5 6 7 Copper I1 I2 Pn ABB t...

Страница 13: ...0 170M6814D JJS 500 2 3 120 2 4 0 4800 414A 5 R9 414 414 250 350 OFAF3H630 170M8554D JJS 600 2 3 150 2 300 MCM 5662 Un 3 phase 575 V 07A4 7 R3 7 0 7 0 5 0 JJS 15 14 106 09A9 7 R3 9 4 9 4 7 5 JJS 20 14...

Страница 14: ...M 30 22 1 185 350 MCM 9 8 7 2 R7 1 54 2 13 95 240 25 150 3 0 400 MCM 4 300 MCM 40 30 29 5 22 1 185 350 MCM 9 8 7 2 R8 2 45 1 77 2 50 150 2 1 0 300 MCM 40 29 5 2 185 2 350 MCM 9 8 7 2 R9 2 54 2 13 2 95...

Страница 15: ...ledge of the safety function The test procedures and report must be documented and signed by this person Validation instructions of the STO function can be found in the drive hardware manual Technical...

Страница 16: ...ucts ACS880 01 11 31 ACS880 04 04F M04 14 34 Safe Torque Off Safe stop 1 Safe stop emergency Safely limited speed Safe maximum speed Safe brake control Prevention of unexpected start up with FSO 12 op...

Отзывы: