ABB ACS880-01 Series Скачать руководство пользователя страница 5

   5

1.

Frames R5…R9: Remove the shroud on the power cable terminals (1a), then make the necessary holes for the cables 

(1b).

Frames R6…R9: Remove the side plates (1a). Remove the shroud (1b), then make the necessary holes for the cables (in 

R8…R9, also do this for the lower shroud).

2. Prepare the power cables:

Remove the rubber grommets from the cable entry.

Frames R1...R3, IP21: Attach the Romex clamps

 

(included in the delivery in a plastic bag) to the cable entry plate holes 

(2a).

Frames R1...R9 IP55: Cut a sufficient hole in the rubber grommet. Slide the grommet onto the cable (2b).

Prepare the ends of the input power cable and motor cable as illustrated in the applicable figure (2c). 

Frames R4...R9 IP21 and frames R1...R9 IP55: Slide the cables through the holes in the cable entry and attach the 

grommets to the holes. 

3. Connect the power cables. For the tightening torques, refer to 

Terminal data

.

 

For frames R1...R3: Ground the cable shields 360 degrees in the Romex clamp (IP21/Type 1 units). For IP55 (Type 12) 

ground the cable shield 360 degrees on grounding shelf as shown in R4...R5 (a). R1...R3 grounding shelf is not shown 

for IP55/Type 12 drive.

For frames R4...R9: Tighten the clamps of the power cable grounding shelf onto the stripped part of the cables (a).

Connect the twisted shield of the cable shields to the grounding terminals (b).

Connect the phase conductors of the motor cable to the T1/U, T2/V and T3/W terminals. Connect the input power 

cable to the L1, L2 and L3 terminals (c). Connect the brake resistor cables to R+ and R- terminals if brake chopper is in 

use (d).

Frames R6…R9: After you have connected the power cables, install the shroud on the terminals.

1b

1a

R4...R5

1a

1b

1c

R6...R9

R8, R9

2b

2c

PE

PE

2a

R1...R3, IP21

R1…R3

T3/W

T2/V

T1/U

UDC-

R+

R-

L3

L2

L1

R4...R5

3b

3b

3a

3a

3b

3c

3b

3c

3b

3c

3c

R1...R3

R1, R2: 1.5 N·m (

13.3 lbf·in)

R3: 2 N·m (

17 lbf·in)

1.5 N·m

R1, R2: 1.5 N·m 
(

13.3 lbf·in)

R3: 2 N·m 

(17 lbf·in)

M4×30
Torx T20
1.2 N·m 
(

10.6 lbf·in)

3d

3d

Содержание ACS880-01 Series

Страница 1: ...After unpacking protect the drive from dust debris and moisture Make sure that these items are included cable conduit box frames R5 R9 of IP21 UL Type 1 drive mounting template control panel quick ins...

Страница 2: ...erial The installation surface is as close to vertical as possible and strong enough to support the drive There is sufficient free space around the drive for cooling maintenance and operation For the...

Страница 3: ...the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and midpoint grounded delta systems IT systems ungrounded or high resistance grounded TT syste...

Страница 4: ...e c Shield of a VFD shielded cable Ground the shield 360 under drive s grounding clamp then twist with the ground conductors and connect under the drive s ground terminal Ground the shield also 360 a...

Страница 5: ...to Terminal data For frames R1 R3 Ground the cable shields 360 degrees in the Romex clamp IP21 Type 1 units For IP55 Type 12 ground the cable shield 360 degrees on grounding shelf as shown in R4 R5 a...

Страница 6: ...als as possible to prevent inductive coupling 1 Cut a hole into the rubber grommet and slide the grommet onto the cable 2 Ground the outer shield of the cable 360 degrees under the grounding clamp Kee...

Страница 7: ...22 COM 23 NO 31 NC Faulted 1 250 V AC 30 V DC 2 A 32 COM 33 NO XD24 Digital interlock 1 DIIL Run enable 2 24VD 24 V DC 200 mA 1 3 DICOM Digital input ground 4 24VD 24 V DC 200 mA 1 5 DIOGND Digital in...

Страница 8: ...1 5 N m 1 5 N m R1 R3 R4 R9 Note Use an un used ground clamp screw If none available ground as shown 1 2 3 2 2 Note The illustration shows frame R2 All frame sizes are similar M4 8 Torx T20 2 N m 17 l...

Страница 9: ...torques refer to Terminal data Frames R4 R5 Install the EMC shroud separating the input and output cabling if not installed yet If brake chopper is in use Connect the brake resistor conductors to the...

Страница 10: ...xt Use the arrow keys and to move the cursor or change values depending on the active view Key shows a context sensitive help page 1 Power up the drive Make sure that you have the motor name plate dat...

Страница 11: ...in the master station 58 05 Parity 8 EVEN 1 default Selects the parity and stop bit setting Use the same setting as in the master station 58 06 Communication control Refresh settings Validates any ch...

Страница 12: ...880 01 Frame size Nominal ratings Fuses3 Typical power cable Typical power loss 8 Input current Output current Motor power1 gG fuse4 DIN 43620 aR fuse2 4 DIN 43620 ULclass T5 6 7 Copper I1 I2 Pn ABB t...

Страница 13: ...0 170M6814D JJS 500 2 3 120 2 4 0 4800 414A 5 R9 414 414 250 350 OFAF3H630 170M8554D JJS 600 2 3 150 2 300 MCM 5662 Un 3 phase 575 V 07A4 7 R3 7 0 7 0 5 0 JJS 15 14 106 09A9 7 R3 9 4 9 4 7 5 JJS 20 14...

Страница 14: ...M 30 22 1 185 350 MCM 9 8 7 2 R7 1 54 2 13 95 240 25 150 3 0 400 MCM 4 300 MCM 40 30 29 5 22 1 185 350 MCM 9 8 7 2 R8 2 45 1 77 2 50 150 2 1 0 300 MCM 40 29 5 2 185 2 350 MCM 9 8 7 2 R9 2 54 2 13 2 95...

Страница 15: ...ledge of the safety function The test procedures and report must be documented and signed by this person Validation instructions of the STO function can be found in the drive hardware manual Technical...

Страница 16: ...ucts ACS880 01 11 31 ACS880 04 04F M04 14 34 Safe Torque Off Safe stop 1 Safe stop emergency Safely limited speed Safe maximum speed Safe brake control Prevention of unexpected start up with FSO 12 op...

Отзывы: