   11

Motor overload protection

The factory motor overload protection is not enabled by default. Motor thermal overload protection can be measured using 

motor temperature devices, can be estimated using a motor model defined by parameters, or can use measured motor 

current and motor Class curves. To enable protection using motor model parameters or measurement devices set 

parameter 

35.11

 and subsequent parameters through 

35.55

. To enable motor Class curves set parameter 

35.56

. Motor 

overload Class is defaulted to 20 and selectable in parameter 

35.57

.

Use the information key ( ) on the drive control panel for more information on setting group 35 parameters. You must set 

the drive overload parameters correctly, or motor damage could occur. 

Fieldbus communication

To configure the embedded fieldbus communication for Modbus RTU, you must set at least these parameters:

Other parameters related to the fieldbus configuration:

Warnings and faults

13.

14.

Parameter

Setting

Description

20.01 Ext1 commands

Embedded 

fieldbus

Selects fieldbus as the source for the start and stop commands when 

EXT1 is selected as the active control location.

22.11 Speed ref1 source

EFB ref1

Selects a reference received through the embedded fieldbus interface 

as speed reference 1.

26.11 Torque ref1 source

EFB ref1

Selects a reference received through the embedded fieldbus interface 

as torque reference 1.

28.11 Frequency ref1 source

EFB ref1

Selects a reference received through the embedded fieldbus interface 

as frequency reference 1.

58.01 Protocol enable

Modbus RTU

Initializes embedded fieldbus communication.

58.03 Node address

1 (default)

Node address. There must be no two nodes with the same node 

address on-line.

58.04 Baud rate

19.2 kbps (default) Defines the communication speed of the link. Use the same setting as 

in the master station.

58.05 Parity

8 EVEN 1 (default) Selects the parity and stop bit setting. Use the same setting as in the 

master station.

58.06 Communication control

Refresh settings

Validates any changed EFB configuration settings. Use this after 

changing any parameters in group 58.

58.14 Communication loss 

action

58.17 Transmit delay

58.28 EFB act1 type

58.34 Word order

58.15 Communication loss 

mode

58.25 Control profile

58.31 EFB act1 transparent 

source

58.101 Data I/O 1 

58.124 Data I/O 24

58.16 Communication loss 

time

58.26 EFB ref1 type

58.33 Addressing mode

Warning

Fault Aux. code

Description

A2A1

2281

Current calibration

Warning: Current calibration is done at the next start.

Fault: Output phase current measurement fault.

-

2310

Overcurrent

The output current is more than the internal limit. This can also be caused by 

an earth fault or phase loss.

A2B3

2330

Earth leakage

A load unbalance that is typically caused by an earth fault in the motor or the 

motor cable.

A2B4

2340

Short circuit

There is a short-circuit in the motor or the motor cable.

-

3130

Input phase loss

The intermediate DC circuit voltage oscillates due to missing input power 

line phase.

-

3181

Wiring or earth fault

Incorrect input and motor cable connection.

A3A1

3210

DC link overvoltage

Intermediate DC circuit voltage is too high.

A3A2

3220

DC link undervoltage

Intermediate DC circuit voltage is too low.

-

3381

Output phase loss

All three phases are not connected to the motor.

-

5090

STO hardware failure

STO hardware diagnostics has detected hardware failure. Contact ABB.

A5A0

5091

Safe torque off

The Safe torque off (STO) function is active.

A7CE

6681

EFB comm loss

Break in embedded fieldbus communication.

A7C1

7510

FBA A communication

Communication lost between drive (or PLC) and fieldbus adapter.

A7AB

-

Extension I/O 

configuration failure

The I/O extension module types and locations specified by parameters do 

not match the detected configuration.

AFF6

-

Identification run

The motor ID run occurs at the next start.

?

Содержание ACS880-01 Series

Страница 1: ...After unpacking protect the drive from dust debris and moisture Make sure that these items are included cable conduit box frames R5 R9 of IP21 UL Type 1 drive mounting template control panel quick ins...

Страница 2: ...erial The installation surface is as close to vertical as possible and strong enough to support the drive There is sufficient free space around the drive for cooling maintenance and operation For the...

Страница 3: ...the measurement again Frame Symmetrically grounded TN S systems center grounded wye Corner grounded delta and midpoint grounded delta systems IT systems ungrounded or high resistance grounded TT syste...

Страница 4: ...e c Shield of a VFD shielded cable Ground the shield 360 under drive s grounding clamp then twist with the ground conductors and connect under the drive s ground terminal Ground the shield also 360 a...

Страница 5: ...to Terminal data For frames R1 R3 Ground the cable shields 360 degrees in the Romex clamp IP21 Type 1 units For IP55 Type 12 ground the cable shield 360 degrees on grounding shelf as shown in R4 R5 a...

Страница 6: ...als as possible to prevent inductive coupling 1 Cut a hole into the rubber grommet and slide the grommet onto the cable 2 Ground the outer shield of the cable 360 degrees under the grounding clamp Kee...

Страница 7: ...22 COM 23 NO 31 NC Faulted 1 250 V AC 30 V DC 2 A 32 COM 33 NO XD24 Digital interlock 1 DIIL Run enable 2 24VD 24 V DC 200 mA 1 3 DICOM Digital input ground 4 24VD 24 V DC 200 mA 1 5 DIOGND Digital in...

Страница 8: ...1 5 N m 1 5 N m R1 R3 R4 R9 Note Use an un used ground clamp screw If none available ground as shown 1 2 3 2 2 Note The illustration shows frame R2 All frame sizes are similar M4 8 Torx T20 2 N m 17 l...

Страница 9: ...torques refer to Terminal data Frames R4 R5 Install the EMC shroud separating the input and output cabling if not installed yet If brake chopper is in use Connect the brake resistor conductors to the...

Страница 10: ...xt Use the arrow keys and to move the cursor or change values depending on the active view Key shows a context sensitive help page 1 Power up the drive Make sure that you have the motor name plate dat...

Страница 11: ...in the master station 58 05 Parity 8 EVEN 1 default Selects the parity and stop bit setting Use the same setting as in the master station 58 06 Communication control Refresh settings Validates any ch...

Страница 12: ...880 01 Frame size Nominal ratings Fuses3 Typical power cable Typical power loss 8 Input current Output current Motor power1 gG fuse4 DIN 43620 aR fuse2 4 DIN 43620 ULclass T5 6 7 Copper I1 I2 Pn ABB t...

Страница 13: ...0 170M6814D JJS 500 2 3 120 2 4 0 4800 414A 5 R9 414 414 250 350 OFAF3H630 170M8554D JJS 600 2 3 150 2 300 MCM 5662 Un 3 phase 575 V 07A4 7 R3 7 0 7 0 5 0 JJS 15 14 106 09A9 7 R3 9 4 9 4 7 5 JJS 20 14...

Страница 14: ...M 30 22 1 185 350 MCM 9 8 7 2 R7 1 54 2 13 95 240 25 150 3 0 400 MCM 4 300 MCM 40 30 29 5 22 1 185 350 MCM 9 8 7 2 R8 2 45 1 77 2 50 150 2 1 0 300 MCM 40 29 5 2 185 2 350 MCM 9 8 7 2 R9 2 54 2 13 2 95...

Страница 15: ...ledge of the safety function The test procedures and report must be documented and signed by this person Validation instructions of the STO function can be found in the drive hardware manual Technical...

Страница 16: ...ucts ACS880 01 11 31 ACS880 04 04F M04 14 34 Safe Torque Off Safe stop 1 Safe stop emergency Safely limited speed Safe maximum speed Safe brake control Prevention of unexpected start up with FSO 12 op...

Отзывы: