Quickstart Guide
ABB PLC and drives integration using Modbus RTU
Modbus
RTU
‐
8
‐
PLC
and
drives
integration
Fieldbus
modules
for
ABB
drives
The
following
ABB
drives
Modbus
RTU
modules
have
an
option
to
activate
built
‐
in
end
termination
and
pull
‐
up/pull
‐
down
resistors.
RMBA
‐
01
(used
with
for
instance
ACS550
and
ACS800)
FSCA
‐
01
(used
with
for
instance
ACS880
and
ACSM1)
The
following
ABB
drives
Modbus
RTU
module
does
not
have
an
option
to
activate
built
‐
in
end
resistors
including
pull
‐
up/pull
‐
down
resistors.
FMBA
‐
01
(used
with
for
instance
ACS355)
Since
the
built
‐
in
end
termination
of
the
modules
(RMBA
‐
01
and
FSCA
‐
01)
automatically
also
activates
pull
‐
up/pull
‐
down
resistors,
it
is
recommended
to
skip
the
built
‐
in
option.
It
is
recommended
to
connect
a
separate
end
termination
resistor
to
the
first
node
(i.e.
the
PLC
COM
interface)
and
the
last
node
(i.e.
the
last
drive
on
the
bus).
For
connection
examples,
see
chapter
“Installation
examples”.
Common
recommendations
Note!
The
following
bullets
are
only
recommendations
and
no
general
rules.
Installation
where
total
cable
length
is
more
than
50
m
o
Use
CPU
AC500
rather
than
AC500
‐
eCo
or
AC500
‐
eCo
with
TK506
RS
485
isolator
for
COM1.
Installation
where
there
is
a
risk
that
ground
connections
in
different
nodes
could
vary
in
voltage
potential
(typically
in
ship
installations
or
with
cable
lengths
more
than
50
m).
o
Use
CPU
AC500
and
do
not
connect
ground
cable,
only
shield
→
2
‐
wire
solution,
or
use
AC500
‐
eCo
with
TK506
RS
485
isolator
for
COM1.
When
AC500
‐
eCo
is
used
o
Use
of
3
‐
wire
connection
is
recommended
because
the
COM
interface
is
not
opto
‐
isolated,
or
use
AC500
‐
eCo
with
TK506
RS
485
isolator
for
COM1.
o
Use
of
cable
length
more
than
50m
should
be
realized
with
repeaters,
or
use
AC500
‐
eCo
with
TK506
RS
485
isolator
for
COM1.
Cable
type
o
Use
only
cables
with
twisted
pair
wires
and
braided
shields.
Foil
shields
are
not
robust
enough,
cannot
be
contacted
well
and
have
poor
HF
(High
Frequency)
properties.
o
Ground
the
cable
shield
directly
with
a
clip
when
entering
the
switch
‐
gear
cabinet.
Do
not
cut
the
shield
until
the
cable
reaches
the
connected
module.
o
The
connection
between
the
PE
bar
and
the
shield
bar
must
have
low
impedance.
o
Use
ABB
cable
TK505
when
suitable
for
easy
installation.