Quickstart Guide
ABB PLC and drives integration using Modbus RTU
Modbus
RTU
‐
9
‐
PLC
and
drives
integration
Bus
line
Construction
2
cores,
twisted,
with
common
shield
Conductor
cross
section
>0.22
mm
2
(24
AWG)
‐
recommendation
0.5
mm
2
corresponds
to
Ø0.8
mm
Twisting
rate
<10/meter
(symmetrically
twisted)
Core
insulation
Polyethylene
(PE)
Resistance
per
core
<100
Ω
/km
Characteristic
impedance
Appr.
120
Ω
(100…150
Ω
)
Capacitance
between
the
cores
<55
nF/km
(if
higher,
then
max
bus
length
must
be
reduced)
Terminating
resistors
120
Ω
,
¼
W
at
both
line
ends
Remarks
Cables
with
PVC
core
insulation
and
a
core
diameter
of
0.8
mm
can
be
used
up
to
a
length
of
appr.
250
m.
In
this
case,
the
bus
terminating
resistor
is
appr.
100
Ω
.
ABB
cable
TK505
For
an
easy
Modbus
installation
in
the
CPU
end,
the
pre
‐
made
ABB
cable
TK505
can
be
used.
It
includes
a
9
pole
D
‐
sub
contact
with
built
‐
in
end
termination
(120
Ω
)
and
pull
‐
up/pull
‐
down
resistors
(2*270
Ω
).
This
contact
is
suitable
for
AC500
‐
eCo
COM1.
It
can
also
be
used
for
AC500
COM2
(even
though
another
voltage
level
is
used),
but
only
if
the
GND
wire
is
not
connected
to
the
Modbus
slaves
(2
‐
wire
solution,
preferred
for
AC500
COM
ports).