Chapter 11 - Changing IGCTs in DIU
ABB
11-2 (6)
3BHS202077 ZAB E01 Rev. C
ACS 6000 Maintenance Manual
The DIU is located in the bottom left corner of a CBU. The CBU is available
in two different sizes depending on the power rating of the converter (size
1 for converters up to 9 MVA and size 2 for converters rated for 9 to 14
MVA).
The replacement of IGCTs is explained using the example of size 1 of the
CBU. Although the space in this type of CBU is very narrow the IGCTs can
be replaced from the front of the cabinet.
1
Check that the drive has been deenergized and voltages have been
removed from the cabinet. See section
11.2 Safety.
2
Disconnect the fiber optic cable (see
Figure 11-1) and the power
supply lead (not shown in
Figure 11-1) of the IGCT to be replaced.
Figure 11-1
Front View of DIU
11.3
Removing an IGCT
Clamp bar
Isolators
IGCTs
Fiber optic cable
Содержание ACS 6000
Страница 6: ...ABB 4 4 3BHS202077 ZAB E01 Rev C ACS 6000 Maintenance Manual...
Страница 14: ...Chapter 2 Checking IGCTs and Diodes ABB 2 6 6 3BHS202077 ZAB E01 Rev C ACS 6000 Maintenance Manual...
Страница 20: ...Chapter 3 Changing Diodes and Thyristors in LSU ABB 3 6 6 3BHS202077 ZAB E01 Rev C ACS 6000 Maintenance Manual...
Страница 30: ...Chapter 4 Changing 3 5 MVA Phase Modules ABB 4 10 10 3BHS202077 ZAB E01 Rev C ACS 6000 Maintenance Manual...
Страница 68: ...Chapter 9 Changing Thyristors in EXU ABB 9 8 8 3BHS202077 ZAB E01 Rev C ACS 6000 Maintenance Manual...
Страница 80: ...Chapter 11 Changing IGCTs in DIU ABB 11 6 6 3BHS202077 ZAB E01 Rev C ACS 6000 Maintenance Manual...
Страница 104: ...Chapter 14 Tightening Torques and Threaded Connections ABB 14 4 4 3BHS202077 ZAB E01 Rev C ACS 6000 Maintenance Manual...