Technical data

Minimum voltage at IN1 and IN2 to be interpreted as “1”: 13 V DC

STO reaction time (shortest detectable break): 1 ms

STO response time: 2 ms (typical), 5 ms (maximum)

Fault detection time: Channels in different states for longer than 200 ms

Fault reaction time: Fault detection time + 10 ms

STO fault indication (parameter 

31.22

) delay: < 500 ms

STO warning indication (parameter 

31.22

) delay: < 1000 ms

Safety integrity level (EN 62061): SIL 3

Performance level (EN ISO 13849-1): PL e

The drive STO is a type A safety component as defined in IEC 61508-2. 
For the full safety data, exact failure rates and failure modes of the STO function, refer to the drive hardware manual.

Markings

The applicable markings are shown on the type designation label of the drive.

Related documents

Declaration of Conformity                                 

CE

ROHS

RCM 

WEEE 

TÜV Nord 

Solar impulse 

Document

Code (English)

ACQ80-01 (30 kW to 55 kW) Drive HW manual

3AXD50001017101

ACQ80 standard control program firmware manual

3AXD50000170654

ACx-AP-x assistant control panels user’s manual

3AUA0000085685

Drive Composer PC tool user's manual

3AUA0000094606

 

 

1/2  

                                                                                                                                                            

  

 

3AXD10000715412 

 

                                                                                                                                                                                        

IMS template code: 3AFE011906, Rev. C

 

 

EU Declaration of Conformity 

Machinery Directive 2006/42/EC  

We 

Manufacturer:  ABB India Limited 

Address: 

Plot No 5 &6 , 2

nd

 Phase , Peenya Industrial Area ,Bangalore,560058, India 

Phone:  

+91 80 22949359 

 

Declare under our sole responsibility that the following product: 

Frequency converter 

 

ACQ80    

ACQ80-04 (frame sizes R0-R3) and ACQ80-01 (frame sizes R4-R5)

 

 

with regard to the safety function 

Safe torque-off 

 

is

 

in conformity with all the relevant safety component requirements of the EU Machinery Directive 

2006/42/EC, when the listed safety function  is used for safety component functionality. 

The following harmonized standards have been applied:  

EN 61800-5-2:2007 

Adjustable speed electrical power drive systems –  

Part 5-2: Safety requirements - Functional 

EN 62061:2021 

Safety of machinery – Functional safety of safety-related electrical, 

electronic and programmable electronic control systems 

EN ISO 13849-1:2015 

Safety of machinery – Safety-related parts of control systems.  

Part 1: General principles for design 

EN ISO 13849-2:2012 

Safety of machinery – Safety-related parts of the control systems. 

Part 2: Validation 

EN 60204-1:2018 

Safety of machinery – Electrical equipment of machines –  

Part 1: General requirements 

 

 

 

 

 

2/2  

                                                                                                                                                        

  

 

3AXD10000715412 

 

                                                                                                                                                                                        

IMS template code: 3AFE011906, Rev. C

 

 

The following other standard has been applied: 

IEC 61508:2010, parts 1-2 

Functional safety of electrical / electronic / programmable 

electronic safety-related systems 

IEC 61800-5-2:2016 

Adjustable speed electrical power drive systems –  

Part 5-2: Safety requirements - Functional 

 

The product referred in this declaration of conformity fulfils the relevant provisions of other 

European Union directives which are notified in a single EU declaration of conformity 

3AXD10000715392. 

Person authorized to compile the technical file 3AXD10000715648:                                                                                      

Name and address: Jussi Vesti, Hiomotie 13, 00380 Helsinki, Finland 

 

Bangalore, 15

th

 March 2023 

Signed for and on behalf of:    

 

 

 

 

 

 

 

 

 

 

 

 

AR  Madhusudhan 

Vice President, MODP 

ABB India Limited

 

Laxmikantha shenoy 

Manager , Prodcut Engineering 

ABB India Limited

 

 

 

 

Содержание ACQ80-01

Страница 1: ...If the drive has not been powered up for a year or more you must reform the DC link capacitors Refer to Capacitor reforming instructions 3BFE64059629 English 3 Select the cables and fuses Select the power cables Obey the local regulations Input power cable ABB recommends to use symmetrical shielded cable VFD cable for the best EMC performance Motor cable Use symmetrical shielded cable VFD cable fo...

Страница 2: ...ights and free space requirements There are no sources of strong magnetic fields such as high current single core conductors or contactor coils near the drive A strong magnetic field can cause interference or inaccuracy in the operation of the drive 5 Install the drive on the wall Select fasteners that comply with local requirements applicable to wall surface materials drive weight and application...

Страница 3: ...3 Frames R4 Put the drive on the wall and tighten the screws Frame R5 IP21 UL Type 1 Install the cable box Frames R5 Put the drive on the wall and tighten the screws 3 1 2 5 4 2 1 3 3 M5 2 1 R5 R5 ...

Страница 4: ...s see the manufacturer s instructions Moisture inside the motor casing decreases the insulation resistance If you think that there is moisture inside the motor casing dry the motor and do the measurement again 10 Connect the power cables Connection diagram shielded cables CAUTION ABB recommends to use a lightning pole to avoid lightning strike to the drive Make sure that the lightening pole ground...

Страница 5: ... than the 3 phase AC pump motors Connection procedure 1 Frames R5 Remove the shroud s on the power cable terminals 2 Prepare the power cables Remove the rubber grommets from the cable entry Cut a sufficient hole in the rubber grommet Slide the grommet onto the cable a Prepare the ends of the input power cable and motor cable as illustrated in the figure b Slide the cables through the holes in the ...

Страница 6: ...ditional PE conductor to the grounding terminal b Tighten the clamps of the power cable grounding shelf onto the stripped part of the cables c Torque the clamps to 1 2 N m 10 6 lbf in If used connect the brake resistor or brake chopper cables 4 Frame R4 Install the grounding shelf 5 Frame R5 Install the cable box plate a and shroud b 6 Attach the cables outside the drive mechanically MOTOR T1 U T2...

Страница 7: ...AGND Analog output circuit common X2 X3 Aux voltage output and programmable digital inputs 10 24V Aux voltage output 24 V DC max 250 mA 11 DGND Aux voltage output common 12 DCOM Digital input common for all 13 DI1 Stop 0 Start 1 14 DI2 Forward 0 Reverse 1 15 DI3 Constant frequency speed selection 16 DI4 Constant frequency speed selection 17 DI5 Ramp set 1 0 Ramp set 2 1 18 DI6 Not configured X6 X7...

Страница 8: ...8 Control cable installation examples This section shows examples for routing the control cables in frame R4 Frame R5 is similar to frame R4 R4 ...

Страница 9: ...d Make sure also that it is safe to start the motor Disconnect the motor from other machinery if there is a risk of damage or injury Use the control panel to do the start up procedure The two commands at the bottom of the display show the functions of the two softkeys and located below the display The commands assigned to the softkeys are different depending on the context Use the arrow keys and t...

Страница 10: ...signals 7 Make additional adjustments for example macro ramps and limits starting from the Main menu Press Menu in the Home view to enter the Main menu Select Primary settings and press Select or With the Primary settings menu you can adjust settings related to the motor PID fieldbus advanced functions and clock region and display You can also reset logs parameters and the control panel Home view ...

Страница 11: ... The output current is more than the internal limit This can also be caused by an earth fault or phase loss A2B3 2330 Earth leakage A load unbalance that is typically caused by an earth fault in the motor or the motor cable A2B4 2340 Short circuit There is a short circuit in the motor or the motor cable 3130 Input phase loss The intermediate DC circuit voltage oscillates due to missing input power...

Страница 12: ...ield of the cable at the control unit only Validation To ensure the safe operation of a safety function a validation test is required The test must be carried out by a competent person with adequate expertise and knowledge of the safety function The test procedures and report must be documented and signed by this person Validation instructions of the STO function can be found in the drive hardware...

Страница 13: ... R4 R5 with regard to the safety function Safe torque off is in conformity with all the relevant safety component requirements of the EU Machinery Directive 2006 42 EC when the listed safety function is used for safety component functionality The following harmonized standards have been applied EN 61800 5 2 2007 Adjustable speed electrical power drive systems Part 5 2 Safety requirements Functiona...

Отзывы: