background image

   11

Fieldbus communication 

To configure the embedded fieldbus communication for Modbus RTU, you must set at least these parameters:

Other parameters related to the fieldbus configuration:

Warnings and faults

Ratings, fuses and typical power cable sizes

Parameter

Setting

Description

20.01 Ext1 commands

Embedded 

fieldbus

Selects fieldbus as the source for the start and stop commands when 

EXT1 is selected as the active control location.

22.11 Ext1 speed ref1

EFB ref1

Selects a reference received through the embedded fieldbus interface 

as speed reference 1. Use this parameter with the vector motor control 

mode.

26.11 Torque ref1 source

EFB ref1

Selects a reference received through the embedded fieldbus interface 

as torque reference 1. Use this parameter with the vector motor 

control mode.

28.11 Ext1 frequency ref1

EFB ref1

Selects a reference received through the embedded fieldbus interface 

as frequency reference 1. Use this parameter with the frequency motor 

control mode.

58.01 Protocol enable

Modbus RTU

Initializes embedded fieldbus communication.

58.03 Node address

1 (default)

Node address. There must be no two nodes with the same node 

address online.

58.04 Baud rate

19.2 kbps (default) Defines the communication speed of the link. Use the same setting as 

in the master station.

58.05 Parity

8 EVEN 1 (default) Selects the parity and stop bit setting. Use the same setting as in the 

master station.

58.14 Communication loss 

action

58.17 Transmit delay

58.28 EFB act1 type

58.34 Word order

58.15 Communication loss 

mode

58.25 Control profile

58.31 EFB act1 transparent 

source

58.101 Data I/O 1 

58.114 Data I/O 14

58.16 Communication loss 

time

58.26 EFB ref1 type

58.33 Addressing mode

Warning

Fault Aux. code

Description

A2A1

2281

Current calibration

Warning: Current calibration is done at the next start.

Fault: Output phase current measurement fault.

A2B1

2310

Overcurrent

The output current is more than the internal limit. This can also be caused by 

an earth fault or phase loss.

A2B3

2330

Earth leakage

A load unbalance that is typically caused by an earth fault in the motor or the 

motor cable.

A2B4

2340

Short circuit

There is a short-circuit in the motor or the motor cable.

-

3130

Input phase loss

The intermediate DC circuit voltage oscillates due to missing input power 

line phase.

-

3181

Wiring or earth fault

Incorrect input and motor cable connection.

A3A1

3210

DC link overvoltage

Intermediate DC circuit voltage is too high.

A3A2

3220

DC link undervoltage

Intermediate DC circuit voltage is too low.

-

3381

Output phase loss

All three phases are not connected to the motor.

-

5090 STO hardware failure

STO hardware diagnostics has detected hardware failure. Contact ABB.

A5A0

5091

Safe torque off

The Safe torque off (STO) function is active.

A7CE

6681

EFB comm loss

Break in embedded fieldbus communication.

A7C1

7510

FBA A communication

Communication lost between drive (or PLC) and fieldbus adapter.

A7AB

-

Extension I/O 

configuration failure

The installed C-type module is not the same as configured, or there is an 

error in the communication between the drive and module.

AFF6

-

Identification run

The motor ID run occurs at the next start.

-

FA81

Safe torque off 1

The Safe torque off circuit 1 is broken.

-

FA82

Safe torque off 2

The Safe torque off circuit 2 is broken.

ACQ80-

01-…

Nominal ratings

Fuses

Typical power 

cable sizes, Cu

Frame 

size

Input 

current

Nominal 

Idc

Output 

current

Motor power

 1)

1) Typical motor power with no overload capacity (nominal use). The kilowatt ratings apply to most IEC 4-pole motors. The 

horsepower ratings apply to most NEMA 4-pole motors.

gG fuse

 (IEC 60269)

DC MCBs

I

1

I

IDC

I

N

P

N

ABB type

A

A

kW

hp

mm

2

U

N

 =3-phase 400 V or 480 V

030kW-4

62

50.78

62

30

40

OFAF000H80

S802PV-S63

3×25 + 16

R4

037kW-4

73

59.79

73

37

50

OFAF000H100 T1D/PV 160 4p F FC 

Cu 1100V DC

3×35 + 16

R4

045kW-4

88

72.07

88

45

60

OFAF000H100 T1D/PV 160 4p F FC 

Cu 1100V DC

3×50 + 25

R5

055kW-4

106

86.81

106

55

75

OFAF00H125

T1D/PV 160 4p F FC 

Cu 1100V DC

3×70 + 35

R5

Содержание ACQ80-01

Страница 1: ...If the drive has not been powered up for a year or more you must reform the DC link capacitors Refer to Capacitor reforming instructions 3BFE64059629 English 3 Select the cables and fuses Select the power cables Obey the local regulations Input power cable ABB recommends to use symmetrical shielded cable VFD cable for the best EMC performance Motor cable Use symmetrical shielded cable VFD cable fo...

Страница 2: ...ights and free space requirements There are no sources of strong magnetic fields such as high current single core conductors or contactor coils near the drive A strong magnetic field can cause interference or inaccuracy in the operation of the drive 5 Install the drive on the wall Select fasteners that comply with local requirements applicable to wall surface materials drive weight and application...

Страница 3: ...3 Frames R4 Put the drive on the wall and tighten the screws Frame R5 IP21 UL Type 1 Install the cable box Frames R5 Put the drive on the wall and tighten the screws 3 1 2 5 4 2 1 3 3 M5 2 1 R5 R5 ...

Страница 4: ...s see the manufacturer s instructions Moisture inside the motor casing decreases the insulation resistance If you think that there is moisture inside the motor casing dry the motor and do the measurement again 10 Connect the power cables Connection diagram shielded cables CAUTION ABB recommends to use a lightning pole to avoid lightning strike to the drive Make sure that the lightening pole ground...

Страница 5: ... than the 3 phase AC pump motors Connection procedure 1 Frames R5 Remove the shroud s on the power cable terminals 2 Prepare the power cables Remove the rubber grommets from the cable entry Cut a sufficient hole in the rubber grommet Slide the grommet onto the cable a Prepare the ends of the input power cable and motor cable as illustrated in the figure b Slide the cables through the holes in the ...

Страница 6: ...ditional PE conductor to the grounding terminal b Tighten the clamps of the power cable grounding shelf onto the stripped part of the cables c Torque the clamps to 1 2 N m 10 6 lbf in If used connect the brake resistor or brake chopper cables 4 Frame R4 Install the grounding shelf 5 Frame R5 Install the cable box plate a and shroud b 6 Attach the cables outside the drive mechanically MOTOR T1 U T2...

Страница 7: ...AGND Analog output circuit common X2 X3 Aux voltage output and programmable digital inputs 10 24V Aux voltage output 24 V DC max 250 mA 11 DGND Aux voltage output common 12 DCOM Digital input common for all 13 DI1 Stop 0 Start 1 14 DI2 Forward 0 Reverse 1 15 DI3 Constant frequency speed selection 16 DI4 Constant frequency speed selection 17 DI5 Ramp set 1 0 Ramp set 2 1 18 DI6 Not configured X6 X7...

Страница 8: ...8 Control cable installation examples This section shows examples for routing the control cables in frame R4 Frame R5 is similar to frame R4 R4 ...

Страница 9: ...d Make sure also that it is safe to start the motor Disconnect the motor from other machinery if there is a risk of damage or injury Use the control panel to do the start up procedure The two commands at the bottom of the display show the functions of the two softkeys and located below the display The commands assigned to the softkeys are different depending on the context Use the arrow keys and t...

Страница 10: ...signals 7 Make additional adjustments for example macro ramps and limits starting from the Main menu Press Menu in the Home view to enter the Main menu Select Primary settings and press Select or With the Primary settings menu you can adjust settings related to the motor PID fieldbus advanced functions and clock region and display You can also reset logs parameters and the control panel Home view ...

Страница 11: ... The output current is more than the internal limit This can also be caused by an earth fault or phase loss A2B3 2330 Earth leakage A load unbalance that is typically caused by an earth fault in the motor or the motor cable A2B4 2340 Short circuit There is a short circuit in the motor or the motor cable 3130 Input phase loss The intermediate DC circuit voltage oscillates due to missing input power...

Страница 12: ...ield of the cable at the control unit only Validation To ensure the safe operation of a safety function a validation test is required The test must be carried out by a competent person with adequate expertise and knowledge of the safety function The test procedures and report must be documented and signed by this person Validation instructions of the STO function can be found in the drive hardware...

Страница 13: ... R4 R5 with regard to the safety function Safe torque off is in conformity with all the relevant safety component requirements of the EU Machinery Directive 2006 42 EC when the listed safety function is used for safety component functionality The following harmonized standards have been applied EN 61800 5 2 2007 Adjustable speed electrical power drive systems Part 5 2 Safety requirements Functiona...

Отзывы: