Terminal data for the power cables

Notes:

 

• 

The minimum specified wire size does not necessarily have sufficient current carrying capacity at maximum load.

• 

The terminals do not accept a conductor that is one size larger than the maximum specified wire size.

• 

The maximum number of conductors per terminal is 1.

Weights and free space requirements

This table shows the requirements for the ambient conditions when the drive is in operation (installed for stationary use).

Ambient conditions

Safe torque off (STO)

The drive has a Safe torque off function (STO) in accordance with IEC/EN 61800-5-2. It can be used, for example, as the final 

actuator device of safety circuits that stop the drive in case of danger (such as an emergency stop circuit).
When activated, the STO function disables the control voltage of the power semiconductors of the drive output stage, thus 

preventing the drive from generating the torque required to rotate the motor. The control program generates an indication 

as defined by parameter 

31.22

. If the motor is running when Safe torque off is activated, it coasts to a stop. Closing the 

activation switch deactivates the STO. Any faults generated must be reset before restarting.
The STO function has a redundant architecture, that is, both channels must be used in the safety function implementation. 

The safety data given is calculated for redundant use, and does not apply if both channels are not used.

WARNING!

 The STO function does not disconnect the voltage from the main and auxiliary circuits of the drive.

Notes:

If stopping by coasting is not acceptable, stop the drive and machinery using the appropriate stop mode before 

activating the STO.

The STO function overrides all other functions of the drive.

Wiring

The safety contacts must open/close within 200 ms of each other.
Double-shielded twisted-pair cable is recommended for the connection. The maximum length of the cabling between the 

switch and the drive control unit is 300 m (1000 ft). Ground the shield of the cable at the control unit only.

Validation

To ensure the safe operation of a safety function, a validation test is required. The test must be carried out by a competent 

person with adequate expertise and knowledge of the safety function. The test procedures and report must be 

documented and signed by this person. Validation instructions of the STO function can be found in the drive hardware 

manual.

Frame 
size

T1/U, T2/V, T3/W, L1, L2, L3, R-, R+/UDC+

PE

Min. wire size (solid/

stranded)

Max. wire size (solid/

stranded)

Tightening torque

Max. wire size (solid/

stranded)

Tightening torque

mm

2

AWG

mm

2

AWG

N·m

lbf·ft

mm

2

AWG

N·m

lbf·ft

R4

0.5/0.5

20

50

1

4.0

3.0

35/35

2

1.5

1.1

R5

6

10

70

2/0

5.6

4.1

-

Frame 

size

Weights

Free space requirements for vertical installation

Stand alone

Side by side

 1)

1) Without free space on the sides.

IP21 (UL 

Type 1)

IP55 (UL 
Type 12)

IP21 (UL Type 1)

IP55 (UL Type 12)

All types

All types

Above

Below

 2)

2) Measured from the drive frame, not from the cable box.

Above

Below

2)

Sides

Above

Below

2)

kg

lb

kg

lb

mm

in

mm

in

mm

in

mm

in

mm

in

mm

in

mm

in

R4

19.0 41.9 20.0 44.1

53

2.1

200

7.9

53

2.0

200

7.9

150

5.9

200

7.9

200

7.9

R5

28.3 62.4 29.0 64.0 100

4.0

200

7.9

100

4.0

200

7.9

150

5.9

200

7.9

200

7.9

Installation altitude

0 … 4000 m (0 … 13123 ft) above sea level. The output current must be derated at 

altitudes above 1000 m (3281 ft). The derating is 1% for each 100 m (328 ft) above 

1000 m (3281 ft). 
Above 2000 m (6562 ft), these grounding systems are permitted: TN-S (center-

grounded wye), TT, and IT (ungrounded or high-resistance symmetrically grounded). 

For the installation requirements for corner-grounded systems at this altitude, contact 

your local ABB representative.

Surrounding air temperature

-15 … +50 °C (5 … 122 °F). No frost permitted. The rated output current must be 

derated by 1% for each 1 °C (1.8 °F) above 40 °C (104 °F). 

Relative humidity

5 … 95%. No condensation permitted. Maximum permitted relative humidity is 60% in 

the presence of corrosive gases.

Contamination levels

(IEC 60721-3-3: 2002)

Chemical gases: Class 3C2.
Solid particles: Class 3S2. No conductive dust permitted.

Vibration (IEC 60068-2)

Max. 1 mm (5 … 13.2 Hz), max. 7 m/s

2

 (13.2 … 100 Hz) sinusoidal

Shock/Drop (ISTA)

Not permitted

Содержание ACQ80-01

Страница 1: ...If the drive has not been powered up for a year or more you must reform the DC link capacitors Refer to Capacitor reforming instructions 3BFE64059629 English 3 Select the cables and fuses Select the power cables Obey the local regulations Input power cable ABB recommends to use symmetrical shielded cable VFD cable for the best EMC performance Motor cable Use symmetrical shielded cable VFD cable fo...

Страница 2: ...ights and free space requirements There are no sources of strong magnetic fields such as high current single core conductors or contactor coils near the drive A strong magnetic field can cause interference or inaccuracy in the operation of the drive 5 Install the drive on the wall Select fasteners that comply with local requirements applicable to wall surface materials drive weight and application...

Страница 3: ...3 Frames R4 Put the drive on the wall and tighten the screws Frame R5 IP21 UL Type 1 Install the cable box Frames R5 Put the drive on the wall and tighten the screws 3 1 2 5 4 2 1 3 3 M5 2 1 R5 R5 ...

Страница 4: ...s see the manufacturer s instructions Moisture inside the motor casing decreases the insulation resistance If you think that there is moisture inside the motor casing dry the motor and do the measurement again 10 Connect the power cables Connection diagram shielded cables CAUTION ABB recommends to use a lightning pole to avoid lightning strike to the drive Make sure that the lightening pole ground...

Страница 5: ... than the 3 phase AC pump motors Connection procedure 1 Frames R5 Remove the shroud s on the power cable terminals 2 Prepare the power cables Remove the rubber grommets from the cable entry Cut a sufficient hole in the rubber grommet Slide the grommet onto the cable a Prepare the ends of the input power cable and motor cable as illustrated in the figure b Slide the cables through the holes in the ...

Страница 6: ...ditional PE conductor to the grounding terminal b Tighten the clamps of the power cable grounding shelf onto the stripped part of the cables c Torque the clamps to 1 2 N m 10 6 lbf in If used connect the brake resistor or brake chopper cables 4 Frame R4 Install the grounding shelf 5 Frame R5 Install the cable box plate a and shroud b 6 Attach the cables outside the drive mechanically MOTOR T1 U T2...

Страница 7: ...AGND Analog output circuit common X2 X3 Aux voltage output and programmable digital inputs 10 24V Aux voltage output 24 V DC max 250 mA 11 DGND Aux voltage output common 12 DCOM Digital input common for all 13 DI1 Stop 0 Start 1 14 DI2 Forward 0 Reverse 1 15 DI3 Constant frequency speed selection 16 DI4 Constant frequency speed selection 17 DI5 Ramp set 1 0 Ramp set 2 1 18 DI6 Not configured X6 X7...

Страница 8: ...8 Control cable installation examples This section shows examples for routing the control cables in frame R4 Frame R5 is similar to frame R4 R4 ...

Страница 9: ...d Make sure also that it is safe to start the motor Disconnect the motor from other machinery if there is a risk of damage or injury Use the control panel to do the start up procedure The two commands at the bottom of the display show the functions of the two softkeys and located below the display The commands assigned to the softkeys are different depending on the context Use the arrow keys and t...

Страница 10: ...signals 7 Make additional adjustments for example macro ramps and limits starting from the Main menu Press Menu in the Home view to enter the Main menu Select Primary settings and press Select or With the Primary settings menu you can adjust settings related to the motor PID fieldbus advanced functions and clock region and display You can also reset logs parameters and the control panel Home view ...

Страница 11: ... The output current is more than the internal limit This can also be caused by an earth fault or phase loss A2B3 2330 Earth leakage A load unbalance that is typically caused by an earth fault in the motor or the motor cable A2B4 2340 Short circuit There is a short circuit in the motor or the motor cable 3130 Input phase loss The intermediate DC circuit voltage oscillates due to missing input power...

Страница 12: ...ield of the cable at the control unit only Validation To ensure the safe operation of a safety function a validation test is required The test must be carried out by a competent person with adequate expertise and knowledge of the safety function The test procedures and report must be documented and signed by this person Validation instructions of the STO function can be found in the drive hardware...

Страница 13: ... R4 R5 with regard to the safety function Safe torque off is in conformity with all the relevant safety component requirements of the EU Machinery Directive 2006 42 EC when the listed safety function is used for safety component functionality The following harmonized standards have been applied EN 61800 5 2 2007 Adjustable speed electrical power drive systems Part 5 2 Safety requirements Functiona...