372 Fieldbus control through the embedded fieldbus interface (EFB)
Control Word
Control Word for the ABB Drives profile
The table below shows the contents of the fieldbus Control Word for the ABB Drives
control profile. The embedded fieldbus interface converts this word to the form in
which it is used in the drive. The upper case boldface text refers to the states shown
in
State transition diagram for the ABB Drives profile
on page
.
Bit
Name
Value
STATE/Description
0
OFF1_
CONTROL
1
Proceed to READY TO OPERATE.
0
Stop along currently active deceleration ramp. Proceed to
OFF1 ACTIVE
; proceed to
READY TO SWITCH ON
unless other interlocks (OFF2, OFF3) are active.
1
OFF2_
CONTROL
1
Continue operation (OFF2 inactive).
0
Emergency OFF, coast to stop.
Proceed to
OFF2 ACTIVE
, proceed to
SWITCH-ON
INHIBITED
.
2
OFF3_
CONTROL
1
Continue operation (OFF3 inactive).
0
Emergency stop, stop within time defined by drive
parameter. Proceed to
OFF3 ACTIVE
; proceed to
SWITCH-ON INHIBITED
.
Warning:
Ensure that the motor and driven machine can
be stopped using this stop mode.
3
INHIBIT_
OPERATION
1
Proceed to
OPERATION D
.
Note:
Run enable signal must be active; see the drive
documentation. If the drive is set to receive the Run
enable signal from the fieldbus, this bit activates the
signal.
0
Inhibit operation. Proceed to
OPERATION INHIBITED
.
4
RAMP_OUT_
ZERO
1
Normal operation. Proceed to
RAMP FUNCTION
GENERATOR: OUTPUT D
.
0
Force Ramp Function Generator output to zero. Drive
ramps to stop (current and DC voltage limits in force).
5
RAMP_HOLD
1
ramp function. Proceed to
RAMP FUNCTION
GENERATOR: ACCELERATOR D
.
0
Halt ramping (Ramp Function Generator output held).
6
RAMP_IN_
ZERO
1
Normal operation. Proceed to
OPERATING
.
Note:
This bit is effective only if the fieldbus interface is
set as the source for this signal by drive parameters.
0
Force Ramp Function Generator input to zero.
7
RESET
0=>1
Fault reset if an active fault exists. Proceed to
SWITCH-
ON INHIBITED
.
Note:
This bit is effective only if the fieldbus interface is
set as the source for this signal by drive parameters.
0
Continue normal operation.
Содержание ACQ580
Страница 1: ...ABB drives for water Firmware manual ACQ580 pump control program ...
Страница 4: ... 2017 ABB Oy All Rights Reserved 3AXD50000035867 Rev C EN EFFECTIVE 2017 06 21 ...
Страница 29: ...Start up control with I O and ID run 25 After the ID run is completed text Done is shown on row ID run ...
Страница 30: ...26 Start up control with I O and ID run ...
Страница 40: ...36 Default configuration ...
Страница 304: ...300 Parameters ...
Страница 340: ...336 Additional parameter data ...
Страница 422: ...Contact us www abb com drives www abb com drivespartners 3AXD50000035867 Rev C EN 2017 06 21 3AXD50000035867C ...