Guidelines for installing the drive to a TT system
The drive can be connected to a TT system under these conditions:
1. Residual current device has been installed in the supply system.
2. This wire has been disconnected. Otherwise EMC filter and ground-to-phase varistor
capacitor leakage current will cause the residual current device to trip.
Ground-to-phase varistor screws
EMC filter screws
Frame
size
VAR
Two EMC screws
R6...R9
VAR
-
R10,
R11
Drive
N
L3
L2
L1
Note:
•
Because the varistor wire has been disconnected, ABB does not guarantee the EMC
category.
•
ABB does not guarantee the functioning of the ground leakage detector built inside
the drive.
•
In large systems the residual current device can trip without a real reason.
Identifying the grounding system of the electrical power
network
WARNING!
Only a qualified electrical professional may do the work instructed in this section.
Depending on the installation site, the work may even be categorized as live
working. Continue only if you are an electrical professional certified for the work.
Obey the local regulations. If you ignore them, injury or death can occur.
To identify the grounding system, examine the supply transformer connection. See the
applicable electrical diagrams of the building. If that is not possible, measure these
Disconnecting EMC filter and ground-to-phase varistor 315
Содержание ACQ580-07
Страница 1: ... ABB DRIVES FOR WATER ACQ580 07 Hardware manual ...
Страница 2: ......
Страница 4: ......
Страница 8: ...4 Update notice ...
Страница 20: ...16 ...
Страница 26: ...Measuring points of frames R6 to R9 are shown below PE L1 L2 L3 22 Safety instructions ...
Страница 32: ...28 ...
Страница 38: ...34 ...
Страница 66: ...62 ...
Страница 69: ...Mechanical installation 65 ...
Страница 73: ... Mechanical installation 69 ...
Страница 75: ...Declaration of Conformity Mechanical installation 71 ...
Страница 108: ...104 ...
Страница 133: ...Electrical installation 129 ...
Страница 134: ...The route of the control cables for frames R10 and R11 is shown below X504 L504 130 Electrical installation ...
Страница 142: ...138 ...
Страница 156: ...152 ...
Страница 162: ...158 ...
Страница 166: ...Replacing the air filters IP54 UL Type 12 Check the air filters and replace if necessary 162 Maintenance ...
Страница 171: ...Maintenance 167 ...
Страница 177: ...3 4 Maintenance 173 ...
Страница 184: ...14 13 15 16 17 Remove the flange 180 Maintenance ...
Страница 187: ...3 4 5 6 Remove the mounting plate Maintenance 183 ...
Страница 189: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 185 ...
Страница 193: ...4 5 3 6 Remove the mounting plate Maintenance 189 ...
Страница 195: ...8 Disconnect the drive module output busbars M12 70 N m 52 lbf ft 7 8 Maintenance 191 ...
Страница 217: ...Frame R6 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS400 DET A Technical data 213 ...
Страница 218: ...Frame R6 Input and motor cable terminal dimensions option F289 DET A 214 Technical data ...
Страница 222: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS250 DET A 218 Technical data ...
Страница 223: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit switch fuse OS400 DET A Technical data 219 ...
Страница 224: ...Frame R7 Input and motor cable terminal dimensions bottom entry and exit option F289 220 Technical data ...
Страница 225: ...Frames R6 and R7 Input and motor cable terminal dimensions top entry and exit options H351 and H353 Technical data 221 ...
Страница 228: ...Frame R8 Input and motor cable terminal dimensions bottom entry and exit option F289 224 Technical data ...
Страница 231: ...Frames R8 and R9 Input and motor cable terminal dimensions top entry and exit options H351 and H353 Technical data 227 ...
Страница 233: ...Frame R9 Input and motor cable terminal dimensions option F289 Technical data 229 ...
Страница 257: ...13 Dimension drawings Example dimension drawings are shown below Dimension drawings 253 ...
Страница 258: ...Frames R6 and R7 IP21 UL Type 1 254 Dimension drawings ...
Страница 259: ...Frames R6 and R7 B054 IP42 UL Type 1 Filtered Dimension drawings 255 ...
Страница 260: ...Frames R6 and R7 B055 IP54 UL Type 12 256 Dimension drawings ...
Страница 261: ...Frames R6 and R7 H351 and H353 top entry and exit Dimension drawings 257 ...
Страница 262: ...Frames R6 and R7 F289 258 Dimension drawings ...
Страница 263: ...Frames R6 and R7 F289 H351 H353 Dimension drawings 259 ...
Страница 264: ...Frames R8 and R9 IP21 UL Type 1 260 Dimension drawings ...
Страница 265: ...Frames R8 and R9 B054 IP42 UL Type 1 Filtered Dimension drawings 261 ...
Страница 266: ...Frames R8 and R9 B055 IP54 UL Type 12 262 Dimension drawings ...
Страница 267: ...Frames R8 and R9 H351 and H353 top entry and exit Dimension drawings 263 ...
Страница 268: ...Frames R8 and R9 F289 264 Dimension drawings ...
Страница 269: ...Frames R8 and R9 F289 H351 H353 Dimension drawings 265 ...
Страница 295: ... Declaration of conformity The Safe torque off function 291 ...
Страница 296: ...292 ...
Страница 302: ...298 ...
Страница 309: ...CMOD 01 multifunction extension module external 24 V AC DC and digital I O 305 ...
Страница 310: ...306 ...
Страница 316: ...312 CMOD 02 multifunction extension module external 24 V AC DC and isolated PTC interface ...
Страница 322: ...318 ...